MODULYS Green Power 

- Ref.: IOMMODGPXX01-GB  00

ENGLISH

OPERATING PROCEDURES

8. 

On line operations

8.1. 

ON LINE operation consists of double conversion operation in conjunction with mains absorption with very low distortion. This 
enables the UPS to supply a voltage that is fully stabilised in frequency and amplitude, regardless of any interference in the mains 
power supply.

ON LINE operation provides three operating modes according to mains and load conditions:

• “Normale” mode.

This is the most frequent operating condition: the energy is drawn from the primary mains power supply and is converted and used 
by the inverter to generate the output voltage to power the loads connected. The inverter is constantly synchronised in frequency 
with the auxiliary mains to enable load transfer (due to an overload or inverter shutdown) without any break in the power supply 
to the load. The battery charger supplies the energy required to maintain or recharge the battery.

• “Bypass” mode.

In case of inverter failure, the load is automatically transferred onto the auxiliary mains without any interruption in the power supply. 
This procedure may occur in the following situations:

-  in the event of a temporary overload, the inverter continues to power the load. If the condition persists, the UPS output is 

switched onto the auxiliary mains via the automatic bypass. Normal operation, which is from inverter, returns automatically a 
few seconds after the overload disappears. 

-  when the voltage generated by the inverter goes is out of tolerances due to a major overload or a fault on the inverter. 

- when the internal temperature exceeds the maximum value allowed.

• “Battery” mode.

In the event of a mains failure (micro interruptions or extended black-outs), the UPS continues to power the load using the energy 
stored in the battery. The mimic panel keeps the user constantly informed on the battery status and on the remaining capacity 
available.

Operation in high effi ciency "Eco-mode"

8.2. 

Operation in ECO-MODE can increase overall efficiency by up to 98% and, at the same time, energy savings can be achieved. If 
the mains supply fails, the UPS will automatically switch onto the inverter and continue to supply power to the load through the 
batteries. Unlike ON LINE operation, operation in ECO-MODE does not provide perfect stability in frequency and voltage; use of 
this mode should therefore be carefully evaluated according to the level of protection required by the application. ECO-MODE is 
not available for parallel connection.

Converter mode

8.3. 

Converter mode enables the UPS to operate as a frequency converter. The available frequency setting for the output is either fixed 
50 Hz or fixed 60 Hz. The AUX MAINS is NOT considered as available in this mode, because AUX MAINS frequency could be 
different from the output frequency. Use 

 or 

 to select the desired frequency, then press 

 to confirm (this setting is only for 

battery start condition or when frequency mode converter is enabled). 

WARNING!

Converter mode has to be set only in case of separated MAINS and AUX MAINS and with AUX MAINS disconnected! 
Do not set in case of common mains as it could damage the load.

Operation with manual maintenance bypass

8.4. 

If the manual bypass is activated (with the appropriate procedure), the load is powered directly from the auxiliary mains, while the 
UPS is in fact excluded from the power supply and can be switched off.

This operating mode is useful when maintenance needs to be carried out on the UPS since service personnel can work on the 
installation without having to cut off the power supply to the load.

Summary of Contents for MODULYS Green Power

Page 1: ...ing manual GB Manual de instalaci n y uso ES Manuel d installation et d utilisation FR Manuale di installazione e uso IT Installatie en bedieningshandleiding NL Dokumentacja Techniczno Ruchowa PL Manu...

Page 2: ...ackaging and in the manual in cases of extended storage or UPS inactivity SOCOMEC UPS may at its own discretion opt for the repair of the product or for the replacement of the faulty or defective part...

Page 3: ...Status LED Indicators for Power Module 17 7 MIMIC PANEL 18 7 1 Mimic panel 18 7 2 Meaning of ideograms 19 7 3 Meaning of the luminous bar 19 7 4 LCD display hierachy 20 8 OPERATING PROCEDURES 21 8 1...

Page 4: ...ay be alive even when the UPS is not connected to the mains Risk of a possible electrocution is possible when the battery is connected to the UPS Therefore do not forget to disconnect the batteries be...

Page 5: ...tion of the symbols used on the labels applied to the unit 1 2 All the precautions and the warnings on the labels and plates on the inside and outside of the equipment should be respected DANGER HIGH...

Page 6: ...ure 2 1 1 A space of at least 5 cm must be left between the cabinets see figure 2 1 1 The UPS switches are accessed from the front however a space of at least 1 5 metres should be left at the front of...

Page 7: ...four pole selective S type differentials load leakage currents are added to those generated by the UPS and during transi tory phases power failure and power return short current peaks may occur If lo...

Page 8: ...module 1 CD including the Instalattion and Operating manuals 1 Quick Start Guide 1 SNMP adapter placed in one of two Communication Slots 1 External battery sensor cable Please immediately contact your...

Page 9: ...where the system is installed 1 2 3 4 1 2 3 4 3 4 1 Place the fixture under the bottom of board to enhance the supporting force Please use No 19 wrench to unsvrew the bolts At least three men needed...

Page 10: ...use this may cause damage of UPS or tip over accident 3 Push the UPS from either front or rear side otherwise could cause tip over accident 4 When the UPS needs a long distance movement make use of a...

Page 11: ...EAR VIEWS 4 AUX MAINS Q2 INPUT Q2 OUTPUT Q3 Q4 BY PASS Q5 225A 225A 225A 225A Mimic panel Parallel port Input Dry Contact Output Dry Contact Q3 Output Power connections Q5 By pass Q4 Aux Mains Q1 Inpu...

Page 12: ...it must be possible to make the neutral of the Emergency Mains line electrically common with the neutral of the main input feed line L1 X10 L2 MAINS SUPPLY L3 N1 L11 X40 X20 L21 AUXILIARY MAINS EXT B...

Page 13: ...nstaller s responsibility to check the electrical compatibility and the presence of appropriate protection devices between the UPS and the battery cabinet fuses and switches of sufficient capacity to...

Page 14: ...oth dip switches to ON position The sum of AUX Mains cable length and OUTPUT cable length must be the same for each system This regulation prevents unbalanced load shared by two UPSs under by pass mod...

Page 15: ...sition The sum of AUX Mains cable length and OUTPUT cable length must be the same for each system This regulation prevents unbalanced load shared by two UPSs under by pass mode i e AUX Mains cable 1 O...

Page 16: ...llow the instructions below to replace or install the Power Module in the system WARNING Before removing any Power Module ensure that the remaining Power Modules can support the load CAUTION Power mod...

Page 17: ...nactive When the locking latch is located at and the main power is turned on the power module is failed FLASHING The power module is failed and off line ON The power module is active Note While releas...

Page 18: ...s bar that identifies the condition of the power supply to the load C alphanumeric information that uses a menu layout to provide details on any alarms that may occur and on the measurements controls...

Page 19: ...de alarm Steady General alarm Flashing 17 Periodic maintenance alarm warning Flashing 18 LAN connection ready cable connected Steady Meaning of the luminous bar 7 3 The luminous bar figure 7 1 1 provi...

Page 20: ...D BYPASS ACTIVE ALARMS BYPASS SETTING COMMISSIONING CLEAR STATISTICS INVERTER OUTPUT OUTPUT SETTING SERIAL NUMBER CLEAR LOG INVERTER OUTPUT BATTERY SETTING FW VERSION MAINTENANCE ALARM INVERTER OUTPUT...

Page 21: ...o interruptions or extended black outs the UPS continues to power the load using the energy stored in the battery The mimic panel keeps the user constantly informed on the battery status and on the re...

Page 22: ...breakers are cut off and switched to OFF as well as the breaker or fuse of the external battery cabinet Confirm if the locking latch is located at position in the power module Confirm if the input po...

Page 23: ...wait about 30 seconds and close Q5 BY PASS 3 Switch off Q1 INPUT 4 Switch off Q4 AUX MAINS 5 Switch off Q3 OUTPUT 6 If there is an external battery cabinet switch off the circuit breaker of battery ca...

Page 24: ...Switching onto the manual bypass creates a direct connection between UPS input and output completely excluding the equipment control part This operation is performed in the event of ordinary maintena...

Page 25: ...e While releasing the locking latch of power module during normal mode the power module is off line and discharges the DC bus until the DC bus voltage reaches safety level Then the LED will be off Pow...

Page 26: ...9 2 11 9 2 6 9 2 4 9 2 7 9 2 2 9 2 10 9 2 10 9 2 1 9 2 9 9 2 5 9 2 8 012 DRWMODGP XX 029 DRWMODGP XX 032 DRWMODGP XX 019 DRWMODGP XX 021 DRWMODGP XX 013 DRWMODGP XX 030 DRWMODGP XX 016 DRWMODGP XX 018...

Page 27: ...act Input Two sets The UPS provides two sets of dry contact input to receive external signals and then the UPS can take corresponding response These contacts belong to normal open type P2 1 2 AC GENER...

Page 28: ...e During installation of the parallel redundancy the parallel communication is abnormal Output overload warning shutdown The loading is over rated output of the UPS Power module fault shutdown The mod...

Page 29: ...packet to wake up PC Send the e mail and SNMP trap to notify users Provides JNC software to protect public operating systems Provides the InsightPower EzSetting software to easily configure for the f...

Page 30: ...80 A phase EMERGENCY OFF E P O Remote E P O ON OUTPUT BREAKER OFF Output breaker not turn on BYP OVERLOAD WARNING 104 overload when UPS is on bypass BAT CABINET OVER HEAT Battery cabinet over 35 C EXT...

Page 31: ...r maximum performance Furthermore during the operating life of the battery Modulys green power stores statistics on the conditions of use of the battery for analysis Since the expected life of the bat...

Page 32: ...20 Power 3 kW 18 Battery charging current A 1 2 5 Efficiency on line mode up to 96 Efficiency eco mode up to 98 Weight kg 30 Environment Operating temperture C 0 to 40 15 to 25 for best battery life S...

Page 33: ......

Page 34: ...ness Park Broadway Lane South Cerney Cirencester GL7 5XL Tel 44 0 1285 863300 info ups uk socomec com OTHER COUNTRIES Tel 34 935 407 575 info ups europe socomec com IN EASTERN EUROPE MIDDLE EAST AFRIC...

Reviews: