Environmental requisites.
2.1.
• The recommended operating temperature, humidity and altitude values are listed in the technical specifications table. Cooling
systems may be required to maintain these values.
• The UPS is not designed for outdoor use. The installation space should be conditioned at temperature of 25 °C and relative humidity
of < 90%. The maximum operation altitude is 3000 m.
• Avoid dusty environments or areas where there is dust from conductive or corrosive materials (e.g. metal dust or chemical solu-
tions).
• The circumstance surrounding the UPS should be kept clean. Prevent any possible damage from mouse or similar objects.
• Do not expose the UPS to direct sunlight or to sources of excessive heat.
• A space of at least 40 cm must be left at the back for adequate ventilation (see figure 2.1-1).
• A space of at least 5 cm must be left between the cabinets (see figure 2.1-1).
The UPS switches are accessed from the front; however, a space of at least 1.5 metres should be left at the front
of the UPS for maintenance purposes. It is also recommended to ensure that the cable connections are sufficiently
long and flexible so that the unit can be extracted during maintenance (see figure 2.1-2).
If it is not possible to leave sufficient space at the front, adequate access must be ensured from both sides.
• The UPS requires good ventilation and heat dissipation. It features fans for heat dissipation. The air flow circulates from front to
the rear bezel.
• It is recommended that you install fire extinguisher beside the UPS for emergency use.
Do not use any air conditioning or similar facility that blows air directly onto the rear side of the UPS.
REQUISITES
2.
2.1-1
MODULYS GP
OR OTHER
CABINET
MODULYS GP
OR OTHER
CABINET
MODULYS GP
OR OTHER
CABINET
MODULYS GP
40 cm
1.5 m
2.1-2
MODULYS GP
40 cm
1,5 m
20 cm
20 cm
5 cm
5 cm
5 cm