NETYS RT Hot Swap 7 - 11 kVA - 551574B - SOCOMEC
12
EN
1.3. Storage and installation
Prior to installation
If the UPS needs to be stored prior to installation, it should be placed in a dry and
well-ventilated area. The allowable storage temperature is between -15°C and
+50°C (5°F~122°F).
After usage
(1) Press and hold the ON/OFF button ( ) for 3 seconds, (2) release it after you
hear one beep, (3) use the Scrolling Up or Down button ( /
) to select ‘Yes’,
and (4) press the Enter button (
) to confirm your selection to turn off the UPS.
Make sure the UPS has shutdown, disconnect the UPS from the utility AC power,
remove all loads/ equipment from the UPS, and store the UPS in a dry and well-
ventilated area at a temperature between -15°C and +50°C (5°F~122°F).
Idle batteries must be recharged fully approximately every three months if the UPS
needs to be stored for an extended period of time. Ensure that, every time after
charging, the battery capacity percentage shown on the LCD of the UPS is 100% (
).
1.4. Installation
Consult the following check list when installing the UPS:
• NETYS RT units are designed for use in enclosed environments.
•
Position the UPS on a flat and stable surface in a properly ventilated room, well
away from heat sources and avoiding direct exposure to sunlight.
• Ambient temperature should be maintained between 0 °C and 40 °C, and relative
humidity below 90% (without condensation); the optimum temperature in terms
of maximizing battery life is 15-20 °C.
• Check that the UPS will not be installed in a dust-laden environment.
• Take care not to stand the UPS or any other heavy object on cables.
• Check that the operating voltage and frequency settings are correct for the mains
power supply at the installation site. Details for the UPS will be found on the data
plate affixed to the top panel.
• For the RS232 serial connection, use only the cables and accessories supplied or
specified by the manufacturer.
PRECAUTIONS IN THE EVENT OF DAMAGE
DO NOT TURN THE BATTERIES UPSIDE DOWN.
Packing materials that have been broken, punctured or torn in such a way as to
reveal the contents must be kept separate in a secure area, and inspected by suitably
qualified staff. Any packing considered unsuitable for shipment of the contents must
be set aside immediately and kept secure, and the sender or recipient contacted.
After storage and before start-up of the UPS, you must allow the UPS to
adjust to room temperature (20°C~25°C or 68°F~77°F) for at least one
hour to avoid moisture condensing inside the UPS.