3. UNPACKING AND INSTALLATION
3.1. UNPACKING
Remove the UPS and all accessories provided (cables, CD-ROMs, etc) from the packing case.
It is always advisable to keep the original packaging which has been specially designed for safe transport, in case the unit has to be moved again.
3.2. ENVIRONMENTAL REQUIREMENTS FOR INSTALLATION
Please read the following before installing the UPS.
• NETYS PL has been designed for use in closed environments.
• Place the UPS on a flat, stable surface, in a ventilated environment away from heat sources and exposure to direct sunlight.
• Keep ambient temperature between 0 °C and 35 °C and humidity less than 90% (non-condensing); the best temperature to
guarantee longest battery lifetime is 15
÷
20 °C.
• Ensure that the environment where the UPS will be installed is not dusty, and leave a space of at least 20 cm around it to allow for
adequate ventilation and access to the rear panel.
• Do not place the UPS or any other heavy object on the cables.
• Check that the voltage and frequency preset for operation is correct for your electrical power supply by consulting the information
on the data plate.
• Use only manufacturer-supplied or recommended cables and accessories for connections to the USB serial interface.
It is recommended that the batteries are charged for 8 hours the first time the unit is used.
• A space of at least 25 cm must be left at the back for adequate ventilation (see figure 3.2-1).
UPS
25 cm
20 cm
20 cm
3.2-1