background image

15

NETYS PR RACK 1U

- Ref.: IOMNETPRXX01-GB  02

ENGLISH

10. TROUBLESHOOTING

This section examines some of most likely problems that can compromise correct operation of the UPS, attempting to solve them 
and identifying the possible causes and remedies.

WARNING!
The UPS internally generates hazardous electrical voltages.
All maintenance must be performed solely and exclusively by authorized personnel.

If you have difficulty in getting the UPS to work, the reason may be among those listed below. For any other problem, you are advised 
to get in touch with your dealer or service organisation directly.

For quick and effective action, when you call it is important to give precise details of the defect, the model number and the manufac-
turing serial number that can be found on the conformance and inspection certificate or on the data plate on the bottom of the UPS.

NOTE: the UPS has an audible alarm feature to alert you of potential power problems. Use Table 8 to determine and resolve the 
UPS alarms and conditions.

10.1. SILENCING AN AUDIBLE ALARM

Before silencing an alarm, check the alarm condition and perform the applicable action to resolve the condition (see Table 8). To 
silence the alarm for an existing fault, press the button. If UPS status changes, the alarm beeps, overriding the previous alarm silencing.

10.2. TROUBLESHOOTING

Legend: 

 = Unlit 

 = Lit 

 = Flashing

Alarm or Condition

Possible Cause

Action

The 

 indicator is not on; the 

UPS does not start.

The power cord is not 
connected correctly.

Check the power cord connections.

The UPS is in Standby mode.

Press and hold the button until you hear the UPS

beep (approximately two seconds) to supply power to the 
connected equipment.

The wall outlet is faulty.

Replace the input fuse with another of the same type or 
reset the automatic switch.

The UPS operates in Battery 
mode only, even though normal 
utility power is present.

The input circuit protector is 
open (230V models only).

Save your work and turn off your equipment. Turn off the 
UPS. Reduce the load, then press the input circuit protec-
tor on the UPS rear panel.

The UPS does not provide the 
expected backup time.

The batteries need charging 
or service.

Plug the UPS into a power outlet for 24 hours to charge 
the battery. Press the 

 button; if the alarm beeps, see 

"Replacing Batteries" on page 40 to replace the battery.

During extended power outages, turn off the UPS after 
saving your work and shutting down your computer to 
conserve battery power.

Normal operation.

None. The UPS is operating in Normal mode and automa-
tically provides consistent voltage with the Buck and Boost 
feature. Power is available to the load segments as indica-
ted by Load 1 (Green) and Load 2 (Green).

  1 beep every 4 seconds.

The UPS is on battery due to 
a utility failure.

The UPS is powering your equipment with battery power. 
Prepare your equipment for shutdown. If this is an exten-
ded power outage, save your work and turn off your 
equipment to conserve battery power.

  

1 beep every 2 seconds.

The battery is running low.

Two minutes or less of battery power remains (depending 
on load configuration and battery charge).

Save your work and turn off your equipment. The alarm 
cannot be silenced.

Summary of Contents for NETYS PR 1000 Rack 1U

Page 1: ...stallation et d utilisation FR Installation and operating manual GB Manuale di installazione e uso IT MK Installatie en bedieningshandleiding NL Dokumentacja Techniczno Ruchowa PL Manual de instala o...

Page 2: ...y temperature poor ventilation etc tampering or any unauthorised repair work During the warranty period SOCOMEC UPS reserves the right to decide whether the product should be repaired or whether to re...

Page 3: ...ECTION 11 7 MODES OF OPERATION 12 7 1 TURNING THE UPS ON 12 7 2 TURNING THE UPS OFF 12 7 3 STANDBY MODE 12 7 4 INITIATING THE SELF TEST 12 8 ADDITIONAL UPS FEATURES 13 8 1 VOLTAGE CONFIGURATION 13 8 2...

Page 4: ...ose of batteries in a fire the battery may explode CAUTION A battery can present a risk of electric shock and high short circuit current The following precaution should be observed when working on bat...

Page 5: ...ower supply which duly filtered and stabilised on models with AVR and if considered suitable is used to supply consumers In cases of a mains failure or if the mains is considered to be outside limits...

Page 6: ...9 Rack 3 1 2 Adjusting the Rail Depth 3 1 3 Securing the Rear Rail 3 1 4 Securing the Front Rail Mounting Bracket M3x6 Bracket Screws Rear Hold Down Bracket Rear Front Assembly Wing Nuts Assembly Wing...

Page 7: ...LLATION 3 1 5 Securing the UPS in a 19 Rack 3 1 6 Rack Tray and Mounting Bracket for a 23 Cabinet 3 1 7 Securing the UPS in a 23 Rack Mounting Bracket M3x6 Bracket Screws Rack Tray NOTE Rails cannot b...

Page 8: ...GB 02 3 INSTALLATION 3 1 8 Zero U Mounting 3 1 9 Mounting the UPS to a Wall Side of Rack Cabinet within 22 54 22 78 or 56 35 56 95 cm WARNING The UPS MUST be positioned with the front panel at the to...

Page 9: ...ef IOMNETPRXX01 GB 02 ENGLISH Load segment 1 green Service red Overload red Load segment 2 green Battery mode yellow Power ON green ON OFF button Test Alarm reset button 4 FRONT VIEW 4 1 2 Control pan...

Page 10: ...e Slot for optional communication boards Slot for optional communication boards Main input socket IEC 320 Main input socket IEC 320 DIP Switches DIP Switches RS232 serial port RS232 serial port USB Po...

Page 11: ...connector 6 1 3 Reinstall the UPS front panel Verify that the UPS is off and unplugged Remove the UPS front panel figure 6 1 1 Connect the battery connector figure 6 1 2 A small amount of arcing may...

Page 12: ...pment and goes into Battery mode 7 2 TURNING THE UPS OFF To turn off the UPS press and hold the button for two seconds and then unplug the UPS from the power outlet If you do not unplug the UPS it rem...

Page 13: ...FF 230 V 207 V 243 V OFF OFF ON 240 V 216 V 254 V ON ON Default position DIP Switch Settings 8 2 NETWORK TRANSIENT PROTECTOR The Network Transient Protector is located on the rear panel and has jacks...

Page 14: ...gh Java Shutdown Client technology Web SNMP card 9 2 RS232 INTERFACE Communication with the server can take place directly via the RS232 interface In addition to local or networked shutdown it is poss...

Page 15: ...correctly Check the power cord connections The UPS is in Standby mode Press and hold the button until you hear the UPS beep approximately two seconds to supply power to the connected equipment The wal...

Page 16: ...to replace the battery Call your service represen tative if the problem persists Continuous beep UPS internal temperature is too high Shutdown is imminent Save your work and turn off your equipment Tu...

Page 17: ...cuit protected Load connection socket IEC 320 4 10 A Battery Typical back up time 12 minutes Battery recharge Advanced charging for faster recovery Approximately 3 hours to 90 usable capacity at nomin...

Page 18: ......

Page 19: ......

Page 20: ...UNITED KINGDOM Units 7A 9A Lakeside Business Park Broadway Lane South Cerney Cirencester GL7 5XL Tel 44 0 1285 863300 info ups uk socomec com OTHER COUNTRIES Tel 34 935 407 575 info ups europe socome...

Reviews: