8. OPERATION
8.1. Single Unit Start-up
Before start-up, ensure that the batteries are fully charged. Before using the
UPS for the first time, please check the battery capacity and the charging
settings. Make sure that you charge the batteries until the battery capacity
percentage shown on the LCD of the UPS is 100% (
).
The configurable battery Quantity is 12, or 16 ~ 22. Please make sure that the
actual battery Quantity is the same as configured on the LCD. Set up the
corresponding charge current based on the total battery amp-hour.
If the UPS connects to an inductive load, the inrush current (initial surge
current) may restart the inverter. To avoid this situation, please turn on the
inductive load in bypass mode before starting up the inverter.
8.1.1. Start-up with AC Input (Single Unit)
1 Verify if the UPS’s input meets with N, L & G of the utility AC power works normally.
2 Switch on the input protective device (see
Figure 7-3
) installed between the
UPS and the utility AC power and switch on the input breaker. After that, the UPS
will enter the Initial Setting Screen (please refer to
9.1 Initial Setting Screen
for more
information).
3 Press and hold the ON/ OFF button ( ) for 3 seconds to start up the UPS.
Release the button after you hear one beep and the UPS will start up. After the
UPS performs self-diagnosis, the UPS will run in ON-LINE mode.