NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
55
EN
ECO Mode
Setup Item
Selectable Value
Default Value
ECO Mode
Disable/ Enable
Disable
ECO Max. Voltage
5-15% (per step: 1%)
+10%
ECO Min. Voltage
5-15% (per step: 1%)
-10%
The setup items ECO Max. Voltage and ECO Min. Voltage will only be
shown on the display when ECO Mode is enabled.
Parallel
The following function is not applicable to the Standard Runtime Model.
Setup Item
Selectable Value
Default Value
Redundant UPS
0-1
0
ID
1-2
1
On/ Off Settings
Setup Item
Selectable Value
Default Value
Energy Saving
Option 1*: Enable/ Disable
Option 2: 1-15mins (per step: 1min)
Option 3: 300W-1500W (per step: 100W)
Disable
Sleep Mode
Option 1: Enable/ Disable
Option 2: 10-120mins (per step: 10mins)
Disable
Auto Restart
Enable/ Disable
Enable
Auto Start on AC
Enable/ Disable
Disable
In the Setting Menu, the sub item Option 1 under the item Energy Saving
cannot be changed.