background image

www.socomec.com

SIRCO 

MOT PV 

UL

Motorised photovoltaic switches

EN

 

INSTR

UCTION

 

MANUAL

Summary of Contents for SIRCO MOT PV UL

Page 1: ...www socomec com SIRCO MOT PV UL Motorised photovoltaic switches EN INSTRUCTION MANUAL ...

Page 2: ...IONS FRAME B8 UL 2000 A 8 3 2 MOUNTING ORIENTATION 8 3 3 ASSEMBLY OF CUSTOMER MOUNTED ACCESSORIES 9 3 3 1 CONNECTION KIT FOR SIRCO MOT PV 2000 A 9 3 3 2 EXTERNAL POWER SUPPLY 400 VAC 230 VAC 9 3 4 FACTORY FITTED ACCESSORY 10 3 4 1 ADDITIONAL AUXILIARY CONTACTS 10 4 CONNECTIONS 11 4 1 POWER CIRCUITS 11 4 2 CONNECTION CONFIGURATION 11 4 3 CONTROL CIRCUITS 12 4 3 1 TYPICAL SIRCO MOT PV WIRING 12 4 3 ...

Page 3: ...ct directly through the mains or indirectly through external circuits Voltages associated with this product may cause injury electric shock burns or death Prior to carry out any maintenance or other work on live parts or other parts in the vicinity of exposed live parts ensure that the switch including all control and associated circuits are de energized DANGER WARNING CAUTION RISK Electric shock ...

Page 4: ...housing 8 Green LED Indication Power SIRCO MOT PV control voltage input within specified range 9 Auto Manual mode selector switch 10 Emergency manual operation Direct Handle 11 Output contacts x 3 Position indication I O and product availability outputs 12 Input contacts x 4 Position order I O Remote control enable Override controls and force to Off position 13 Red LED Indication Product Unavailab...

Page 5: ...al incoming and outgoing wiring details 2 Complete SIRCO MOT PV product current rating and reference number label serial number barcode and UL marking 3 Emergency manual operation direction of rotation indication label 4 Auxiliary power supply contacts identification label 5 Motor barcode and serial number 6 Output contacts identification label 7 Input contacts identification label ...

Page 6: ...9 40 C 50 C 104 F 122 F 0 8 50 C 60 C 122 F 140 F 0 7 60 C 70 C 140 F 158 F 2 3 2 2 Hygrometry 80 humidity without condensation at 55 C 131 F 95 humidity without condensation at 40 C 104 F 2 3 2 3 Altitude Up to 2000m in altitude without derating For higher altitude the Ka correction factors below apply Ka Correction Factor 2000 m A 3000 m 3000 m A 4000 m Ue 0 95 0 8 Ie 0 85 0 85 2 3 3 Storage Con...

Page 7: ...accessory DOOR ESCUTCHEON PLATE An accessory to be fixed onto a cabinet door to frame the motor part of flush mounted SIRCO MOT PV switches CONTROL VOLTAGE TRANSFORMER Allows a standard 230 V AC device to be supplied with 400 Vac Others Refer to the end of this instruction manual or the latest SOCOMEC product catalogue Downloadable from www socomec com 2 4 2 Factory fitted accessory SUPPLEMENTARY ...

Page 8: ...20 4 72 120 0 59 15 0 19 5 0 19 5 0 49 12 5 0 98 25 0 98 25 1 18 30 1 18 30 1 77 45 1 77 45 3 54 90 1 2 5 4 3 Ø0 19 Ø12 5 1 Padlocking Facility Locking bracket for up to 3 padlocks min Ø 0 16 in Ø 4 mm max Ø 0 31 in Ø 8 mm 2 Emergency manual operation Maximum operating radius with an operating angle of 90 3 Phase Barriers 4 Flush mounting cutout dimensions for front door 5 Emergency removable hand...

Page 9: ...tity indicated by the number of poles 4 poles 1 Conditions of use of these products may lead to a derating 3 3 2 External Power supply 400 Vac 230 Vac Power Transformer intended for 400Vac Phase to Phase voltage applications that do not provide the availability of a neutral conductor Transformer data 400Vac 230Vac 200VA 301 302 230 Vac 12Vdc 301 302 230 Vac 400Vac 301 302 230 Vac 24Vdc DC power su...

Page 10: ...itions 0 and I Up to 2 additional NO NC auxiliary contacts can be fitted 81 81 82 84 91 92 94 Pos I Pos I 82 84 91 92 94 2000 A Standard Denomination Terminal Description Characteristics Recommended Cable Section Additional Aux Contact Included 81 91 Common Dry Contacts 2A AC1 250V 1 5 2 5 mm2 82 92 Normally Closed Contact 84 94 Normally Open Contact ...

Page 11: ...ount the connection cable lengths and or others environmental specific operating conditions 2000 A Frame size B8 UL Maximum bars width Cu 3 94 in 100 mm Tightening torque min max 354 398 lb in 40 45 Nm 4 2 Connection configuration Kit ref 2609 1200 MANDATORY 2P 2P CHARGE LOAD CHARGE LOAD ...

Page 12: ...314 316317 63A64A 04 24 13 Fus 4A type gG 230 Vac Source PV LOAD Source PV Control Inputs from Remote pushbuttons PLC Controller CAUTION Verify that the Auxiliary power supply feeding terminals 301 and 302 are within the limits of 208Vac 277Vac 20 166 332Vac DANGER Do not handle any control or power cables connected to the SIRCO MOT PV when voltage may be present ...

Page 13: ...9PV4160 4 TETR 75A434 2000A Ue 1000V 19PV4200 4 TETR 75A436 3200A Ue 1000V 19PV4320 4 TETR 1 2 3 4 5 6 75A413 200A Ue 750V 19PV3020 3 TRI 75A414 250A Ue 750V 19PV3025 3 TRI 75A415 400A Ue 750V 19PV3040 3 TRI 75A416 500A Ue 750V 19PV3050 3 TRI 75A417 630A Ue 750V 19PV3063 3 TRI 75A425 200A Ue 1000V 19PV4020 4 TETRA 75A426 250A Ue 1000V 19PV4025 4 TETRA 75A427 400A Ue 1000V 19PV4040 4 TETRA 75A428 5...

Page 14: ...th the handle for manual operation removed Turning the selector switch to from AUT and back to AUT resets a fault state Emergency manual operation The SIRCO MOT PV can be manually operated whilst retaining the electrical characteristics and performance of the power switching function This function is usually used in case of emergencies or during maintenance To operate the SIRCO MOT PV manually ens...

Page 15: ...250A Ue 1000V 75A427 400A Ue 1000V 75A428 500A Ue 1000V 75A429 630A Ue 1000V 75A430 I800A Ue 1000V 75A431 1000A Ue 1000V 75A432 1250A Ue 1000V 75A433 1600A Ue 1000V 75A434 2000A Ue 1000V 75A436 3200A Ue 1000V Pulse duration for activation of contact inputs 60ms Pin 312 Remote Control Mode Enable when closed with 317 This contact must be closed with 317 so as to activate all control inputs except f...

Page 16: ...by simply bridging terminals 316 and 317 NOTE 313 317 closed Force SIRCO MOT PV to OFF Position takes priority over all other orders no matter of the control logic used Impulse logic standard configuration The SIRCO MOT PV is driven to a stable position I O after receiving an impulse order A switching command of at least 60 ms is necessary to initiate the switching operation When switching command...

Page 17: ...nutes This test ensures that the SIRCO MOT PV is operational in terms of control inputs Should one of the tests fail a second test is performed to reconfirm the error state Should the SIRCO MOT PV motorisation module become unavailable contact 63A 64A are opened the power ready LED s are switched off and the fault LED is activated The fault LED will remain active for as long as sufficient power is...

Page 18: ...d to external order I O Verify the selected control logic wiring impulse or contactor Verify the connector connections The fault manuel LED is ON The FAULT MANUAL LED is on when in manual mode this is normal and in AUT Mode when there is an internal fault in the SIRCO MOT PV To reset a fault condition switch the SIRCO MOT PV from AUT to Manu and back to AUT Should the fault LED remain on you will ...

Page 19: ...19 EN SIRCO MOT PV UL 545 672 B SOCOMEC ...

Page 20: ...545 672 B EN 04 16 Non contractual document 2016 Socomec SAS All rights reserved SOCOMEC R C S Strasbourg B 548 500 149 B P 60010 1 rue de Westhouse F 67235 Benfeld Cedex www socomec com ...