STATYS
Jbus / Modbus serial link
OPMSTAJB0810-GB_01 7
ENGLISH
6.
J
buS
/m
odbuS
l
Ink
6. 1.
S
erIal
lInk
1
and
2
deFault
SettIngS
Baud rate:
9600 bauds
Parity:
NONE
Data:
8 bits
Stop:
1 bit
Slave:
1
The serial link settings can be set from the control panel or from the graphic touch screen.
6. 2.
H
ow
to
cHange
tHe
SerIal
lInk
SettIngS
?
Available baud rate: 4800 - 9600 - 19200 bauds
Parity:
EVEN - ODD - NONE
Slave number:
1 to 255
Settings menu of the LCD mimic panel type D20 (see the operating manual):
6. 2-1
Modbus link configuration (user access)
Display: mod bus
Slave number
Display: sla nb
Default value: 1
Possible choice: 1 to 255
Link speed
Display: bds
Default value: 9600
Possible choice: 2400, 4800, 9600 or 19200
Link parity
Display: par
Default value: no
Possible choice: odd, eve (even) or no
Settings screen of the Graphic mimic panel type ADICOM (see the operating manual):
«Type» should be setup at Modbus mode.