8.5. Operating
statuses
Operating phases
Status
Description
Maintenance Mode
Maintenance mode enabled.
Standby
Inverter in standby due to remote Stop command or manual setting on the display.
Sleep Mode
Sleep mode, insufficient radiation.
If Sleep Mode remains on during the day when there is plenty of radiation, check the photovol-
taic panel exposure, the photovoltaic system wiring and the polarity of the DC connections to
the inverter. Otherwise, contact the Support Service.
Low Radiation
Insufficient radiation for connection to the mains network.
AC Network Check
Check electricity mains network parameters fall within the range.
Insulation Check
Check insulation resistance to earth.
Startup Conditions Check
Check for sufficient energy originating from the photovoltaic field.
Check in progress
Check GFCI and test AC output contactors.
Inverter ON
Inverter working properly.
Inverter OFF due to alarm
Inverter stopped due an alarm being detected.
Standard statuses
Code
Status
Description
S66
AC Network OK
AC voltage and frequency within the range of tolerance.
S67
Inverter ON
Inverter working properly.
S80
Reactive Compensation
The inverter is managing reactive power in accordance with national standards.