TROUBLESHOOTING HANDLING
110
HYD 5K...20KTL-3PH
1.
Press the "Back" on the main interface to enter the main menu
page, and select Advanced Settings - On/off machine control -
Shutdown. Make the inverter shut down safely.
Note: after using the menu setting to shut down the inverter, the
inverter should be checked and reenergising, it still needs to be
on the main menu page. Select advanced Settings - switch
machine control - start up to enable the inverter to start up and
run.
2.
Disconnect the AC circuit breaker connecting the inverter power
grid port to the power grid.
3.
Disconnect the AC breaker connecting the inverter load port to
the emergency load.
4.
Disconnect the PV side DC switch.
5.
Turn off the battery and disconnect the DC switch between the
battery and the inverter.
6.
Wait for 5 minutes before checking the inverter.
7.
Follow the steps below to view recorded problems: Press “Back”
to enter the main menu in the normal interface. In the interface
screen select "Event List", then press “OK” to enter events.
8.1.2
Earth fault alarm
This inverter is compliant with IEC 62109-2 Clause 13.9 and AS/NZS
5033 for earth fault protection.
If an earth fault alarm occurs, the error is displayed on the LCD
screen, the red light illuminates and the error can be found in the
error history log.