ELECTRICAL CONNECTIONS
HYD 5K...20KTL-3PH
77
parameters on the menu interface of the inverter. Refer to Advanced
settings / 3 Anti Reflux in this manual for specific operation methods.
Hard anti-reverse current is enabled by default in some safety
settings.
NOTE
•
Adjusting the hard anti-reverse current setting requires
permission from SOFARSOLAR.
•
Only installers and distributors have the permission to use
the Bluetooth APP for enabling/disabling settings, and
setting up the feed-in limitation function. Refer to
Advanced settings / 3 Anti Reflux in this manual for
specific operation methods.
5.10.2
Obtaining grid information via System B and C
Follow the wiring instructions according to the wiring method as
shown in single line diagram for System B or System C, enable the
Anti-Reflux Power function and set the limitation parameters on the
menu interface of the inverter.
The configuration of the hard feed-in limitation control follows the
same steps as that of System A. The electricity meter function will
also need to be enabled via the menu interface of the machine. Refer
to 7.4.2 Advanced settings → 3 Anti Reflux in this manual for the
specific operation methods.