COMMISSIONING THE INVERTER
86
HYD 5K...20KTL-3PH
8.
For lithium battery, please ensure that the communication cable
has been correctly connected.
9.
For the lead-acid battery, please ensure that the NTC wire has
been correctly connected.
6.3
Starting the inverter
Please follow below steps to switch the inverter ON.
1.
Make sure there's no power generation in inverter's phase.
2.
Turn ON DC switch.
3.
Switch ON the battery. Turn ON DC isolator between battery &
inverter.
4.
Turn ON AC circuit breaker between the inverter GRID port &
GRID.
5.
Turn ON AC circuit breaker between the inverter LOAD port &
critical load.
6.
Inverter should start to operate now.
6.4
Initial setup
You need to set the following parameters before inverter starts to
operate.
Parameter
Note
1) Language setting
The default is English
2) System time setting
If you are connected to the server
or using the App, the time is set to
the local time automatically