HYD 3K~6K-EP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
。
- 42 -
Test 27.S2 OK!
↓
Wait
Testing 81>S1...
↓
Wait
Test 81>S1 OK!
↓
Wait
Testing 81>S2…
↓
Wait
Test 81>S2 OK!
↓
Wait
Testing 81<S1...
↓
Wait
Test 81<S1 OK!
↓
Wait
Testing 81<S2...
↓
Wait
Test 81<S2 OK!
↓
Press “Ok”
Auto Test OK!
↓
Press “Down”
59.S1 threshold 253V 900ms
↓
Press “Down”
59.S1: 228V 902ms
↓
Press “Down”
59.S2 threshold 264.5V
200ms
↓
Press “Down”
59.S2: 229V 204ms
↓
Press “Down”
27.S1 threshold 195.5V
400ms
↓
Press “Down”
27.S1: 228V 408ms
↓
Press “Down”
27.S2 threshold 92V 200ms
↓
Press “Down”
27.S2: 227V 205ms
↓
Press “Down”
81>.S1 threshold 50.5Hz
100ms
↓
Press “Down”
81>.S1 49.9Hz 103ms
↓
Press “Down”
81>.S2 threshold 51.5Hz
100ms
↓
Press “Down”