Product Description

REMOTE PORT

Vin+

AC FAILURE

BATLOW

S.D.

S.D.

S.D. TEST

BAT LOW

AC FAILURE

3.73 (94.6)

2.59 (65.7)

.591 (15.0)

3.09 (78.4)

3.84 (88.4)

.20 (5.0)

1.26 (32.0)

All dimensions are in inches (mm)

Front and Rear Views

1.

 

Vin:

 Input connector used to provide the dry contact relay with 12 V dc 

input power.

2.

 

Remote Port:

 The communication port is used for linking to the SDU UPS.

  Note:

 The provided connection cable is used only for this dry contact relay.

3.

 

AC Failure Indicator:

 This yellow LED is illuminated when ac voltage is 

abnormal.

4.

 

Battery Low Indicator:

 This green LED is illuminated when battery 

capacity is low.

5. Shut Down Indicator (S.D.):

 When the dry contact relay receives the 

shut down signal for 1 second, the red LED is illuminated and the SDU 

UPS goes into the shut down mode.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Summary of Contents for RELAYCARD-SDU

Page 1: ...Dry Contact Relay Kit RELAYCARD SDU Instruction Manual Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 2: ...rom use of this information or for any errors or omissions 2007 Sola Hevi Duty All rights reserved throughout the world Specifications are subject to change without notice Sola Hevi Duty name and logo are registered trademarks of EGS Electrical Group LLC All names referred to are trademarks or registered trademarks of their respective owners Buy www ValinOnline com Phone 844 385 3099 Email Custome...

Page 3: ... cable into the 12 V dc output of the SDU UPS Plug the other end of the power interconnection cable into the input of the relay box 3 Plug the DB 9 connector cable into the RS232 communication port of the SDU UPS Plug the other end of the connector into the remote port of the dry contact relay Only qualified personnel should install or service this system Electrical safety precautions must be foll...

Page 4: ...on port is used for linking to the SDU UPS Note The provided connection cable is used only for this dry contact relay 3 AC Failure Indicator This yellow LED is illuminated when ac voltage is abnormal 4 Battery Low Indicator This green LED is illuminated when battery capacity is low 5 Shut Down Indicator S D When the dry contact relay receives the shut down signal for 1 second the red LED is illumi...

Page 5: ... after 3 minutes 7 8 Pole Terminal Blocks 1 2 3 4 5 6 8 7 C N C A R U L I A F C E W O L T A B D S C N C _ _ Terminal Block Layout and Operation UPS State External Input DCB LED Display Terminal Blocks O Occur X Does not occur O Enable X Disable O LED On X LED Off O Close X Open Ac Failure BAT Low S D Yellow Green Red Pin 1 2 Pin 2 3 Pin 4 5 Pin 5 6 X X X X X X X O X O O X X O X X O X X O O O X X O...

Page 6: ...t maximum current 1 0 A 250 V ac 3 Shut down input signal range 5 V to 12 V can be provided by enabling terminals 7 and 8 for remote shut down control assured by an external remote device Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Reviews: