30
| 7.0 Controls & indicators
7.0 Controls & indicators
Battery Level indicators
L1 Load Level indicators
L2 Load Level indicators
Bypass indicator
Inverter indicator
On/Alarm Silence/
Manual Battery
Test button
Standby/Manual
Bypass button
Fault indicator
Ac Input indicator
Battery indicator
Figure 23: Operation and display panel
7.1 On/Alarm Silence/Manual Battery Test Button
This button controls output power to connected load(s) and has three functions:
•
On:
Pressing this button for 4 seconds will start the UPS.
•
Alarm Silence:
To silence alarms, press this button for at least one second. After the alarm is silenced, the S4KC will
reactivate the alarm system to alert of additional problems.
NOTE:
The Low Battery and Bypass reminder alarms CAnnOT be silenced.
•
Manual Battery Test:
To initiate a manual battery test, press the On button for at least one second while operating
from utility power with no alarm conditions present. if only three of the five Battery LEDs illuminate, allow the UPS
to recharge the batteries for 24 hours. After 24 hours, retest the batteries.
After the batteries have been retested, if only three of the five Battery LEDs illuminate, contact your local dealer,
SolaHD representative, or SolaHD Technical Support.