S4K2UC SEriES USEr MAnUAl |
15
2.0 installation
2.1 Unpacking & Inspection
Unpack the UPS and conduct the following checks:
♦
Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and your local dealer or
SolaHD representative immediately.
♦
Check the accessories against the delivery list. If there are any discrepancies, contact your local dealer or SolaHD repre-
sentative immediately.
2.2 What’s Included
♦
Compact disk containing: MultiLink, configuration program and user manual
♦
One, 6-1/2 ft. (2 m) long USB cable
♦
Mounting hardware, including screws and handles
♦
Two plastic tower stand sets (four pieces total)
♦
Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
NOTE:
The S4K2UC external battery cabinet shipping package includes one battery cabinet, two spacers for tower configu-
ration and one dc power cable.
2.3 Preparation for Installation
2.3.1 Installation Environment
♦
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. The installation environ-
ment should meet the specifications listed in “9.0 Specifications”.
♦
Place the UPS in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives,
and conductive contaminants. Avoid direct sunlight.
NOTE:
Operating the UPS in temperatures above 25°C (77°F) reduces battery life.
2.3.2 Installation Clearances
Maintain at least 4 inches (100 mm) clearance in the front and rear of the UPS. Do not obstruct the air inlets on the front
panel and rear panel of the UPS; blocking the air inlets reduces ventilation and heat dissipation, shortening the service life of
the unit.