44
| 9.0 Specifications
Table 13: Operating Temperature Parameters
Ambient temperature
+25°C to +30°C [+77°f to +86°f]
+30°C to +35°C [+86°f to +95°f] +35°C to +40°C [+95°f to +104°f]
Maximum output power factor derating at
maximum load
100% to 93%
93% to 86%
86% to 79%
Table 14: Battery Backup Times
Number of
Batteries
Model
VA
1
Backup Time (minutes) at load (watts)
2
200
W
400
W
600
W
800
W
1000
W
1200
W
1400
W
1600
W
1800
W
2000
W
2500
W
100% load
Minutes
Min.
W
Internal battery
700
26
14
6
--
--
--
--
--
--
--
--
6
630
1000
28
15
9
5
--
--
--
--
--
--
--
4
900
1500
--
26
16
10
8
5
--
--
--
--
--
4
1350
2000
--
--
20
11
10
8
6
5
4
--
--
4
1800
3000
--
--
--
25
20
14
10
9
8
5
4
4
2700
Internal b
1 external battery
cabinet
700
126
78
54
--
--
--
--
--
--
--
--
50
630
1000
128
74
52
41
--
--
--
--
--
--
--
27
900
1500
--
110
72
48
36
28
--
--
--
--
--
24
1350
2000
--
--
54
34
34
26
22
17
15
--
--
15
1800
3000
--
--
--
102
80
56
50
44
38
26
22
18
2700
Internal b
2 external battery
cabinets
700
264
122
88
--
--
--
--
--
--
--
--
82
630
1000
252
126
84
60
--
--
--
--
--
--
--
58
900
1500
--
208
132
94
74
54
--
--
--
--
--
48
1350
2000
--
--
120
82
60
52
44
36
29
--
--
29
1800
3000
--
--
--
124
114
106
92
74
66
62
46
44
2700
Internal b
3 external battery
cabinets
700
280
140
120
--
--
--
--
--
--
--
--
116
630
1000
320
148
118
80
--
--
--
--
--
--
--
78
900
1500
--
310
204
138
102
90
--
--
--
--
--
82
1350
2000
--
--
180
126
92
72
62
52
45
--
--
45
1800
3000
--
--
--
174
150
122
110
105
104
76
62
62
2700
Internal b
4 external battery
cabinet
700
560
300
146
--
--
--
--
--
--
--
--
140
630
1000
600
250
138
116
--
--
--
--
--
--
--
109
900
1500
--
400
256
180
144
110
--
--
--
--
--
100
1350
2000
--
--
240
166
130
108
94
84
64
--
--
64
1800
3000
--
--
--
184
172
150
128
120
119
105
92
84
2700
1
Backup times are valid for all models rated with the listed VA
2
Approximate backup times are in minutes and at +25°C [+77°f] with a resistive load