6.0 Configuration Program
The final step of installation may require custom configuration of your UPS using the enclosed configuration program
(located on the CD). Some configuration settings may be changed only while the UPS is off. These settings should be set
before the UPS is put into service powering critical loads.
6.1 Configuration Program Features
•
Select L–n output voltages to match local voltages.
•
Enable/Disable Auto-restart.
•
Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.
•
Set the Low Battery alarm time to a value of 2 to 30 minutes.
•
Enable/Disable the Auto-Battery Test.
•
Set the Auto-Battery Test for 7, 14, 21, or 28 days.
•
Specify the number of external battery cabinets connected to the UPS to adjust the remaining backup time calcula-
tions reported by software products.
•
modify the shutdown setting of the terminal block.
6.1.1 What You Will Need
in addition to the S4KC UPS, you will need the configuration program (located on the CD) and USB cable; both are included
in the UPS accessory box. A Windows 95® or later computer, desktop, or laptop with a USB port is also required to set up and
run the configuration program.