50
| 12.0
Specifications
Table 9: Internal Battery Specifications
Parameters
Model Number
S4K144INTBATC
S4K288INTBATC
Used with
6000 VA models
10000 VA models
DIMENSIONS, w x D x H, in. [mm]
Unit
2.8 x 19.3 x 8.1 [70 x 490 x 206]
5.3 x 19.7 x 8.1 [135 x 500 x 207]
Shipping
12.2 x 23.7 x 10.3 [310 x 602 x 262]
12.2 x 23.9 x 9.5 [310 x 607 x 242]
wEIgHT, lb. [kg]
Unit
75.8 [34.4]
71.1 [32.3]
Shipping
81.1 [36.8]
76.4 [34.7]
BATTERy PARAMETERS
Type
Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V x Rating
2 x 6 x 12 V x 8.5 Ah
2 x 12 x 12 V x 8.5 Ah
Battery Mfr./Part Number
Panasonic/UP-rW1245; CSB/Hr 1234W F2
Backup Time
See Table 13
Recharge Time
3 hours to 90% capacity after full discharge into 100% load
ENVIRONMENTAL REqUIREMENTS
Operating Temperature
0°C to +40°C [+32°F to +104°F]; See Table 8 for operating temperature parameters
Storage Temperature
-15°C to +50°C [+5°F to +122°F]
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. [3,000 m]
AgENCy
Safety
UL1778, cUL Listed, not for use in a computer room as defined in the standard
for the protect of Electronic Computer/Data Processing Equipment AnSi/nFPA 75
RFI/EMI
FCC Part 15, Subpart B, Class A
Transportation
iSTA Procedure 1A