S4KC SEriES USEr mAnUAL |
53
Table 13: Battery Backup Times
Number of Batteries/Cabinets
Load % of
Capacity
Model Rating
6000 VA
10000 VA
Backup Time in Minutes
Internal battery
10%
94
100
20%
43
46
30%
26
28
40%
17
18
50%
13
14
60%
10
11
70%
8
9
80%
6
7
90%
5
6
100%
4
5
Internal b 1 external battery cabinet
10%
154
159
20%
96
102
30%
53
65
40%
44
46
50%
34
37
60%
26
28
70%
21
23
80%
17
18
90%
15
16
100%
13
14
Internal b 2 external battery cabinets
10%
201
210
20%
136
141
30%
97
103
40%
69
74
50%
50
52
60%
44
46
70%
37
40
80%
31
34
90%
26
28
100%
22
25
Internal b 3 external battery cabinets
10%
304
310
20%
156
160
30%
127
133
40%
97
103
50%
74
79
60%
60
65
70%
49
51
80%
44
46
90%
39
42
100%
34
37
Internal b 4 external battery cabinets
10%
322
327
20%
180
190
30%
145
149
40%
122
128
50%
98
103
60%
77
82
70%
66
71
80%
52
60
90%
48
50
100%
44
46
Using the configuration program, the user may specify the number of external battery cabinets attached to the UPS.
The factory default is programmed for internal batteries only. Table 13 shows the estimated battery backup times at
different loads.