background image

S4KC SEriES USEr MAnUAL  | 

33

9.2.2 Battery Mode Shutdown

Battery Mode Shutdown permits shutting down the UPS by turning off the rectifier, inverter, and static switch so that 

there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active. Activation of 

the Battery Mode Shutdown will be logged as an event in the event history log.

Battery Mode Shutdown can be performed locally or remotely:

• 

Local

 Battery Mode shutdown can be performed by shorting the Pins in Set 4.

• 

Remote

 Battery Mode Shutdown can be performed using a switch connected to the Pins in Set 4 and mounted at a 

remote location.

NOTES:

• 

remote Power Off will be performed by nO contact.

• 

The current limited source for the opto coupler (+12 V dc, 50 mA) will be available from the UPS.

• 

The connection to the UPS for remote connection will be via terminal block connector.

• 

Battery Mode Shutdown wiring must conform to all national, regional, and local wiring codes and laws.

• 

This signal must last for 1.5 seconds or longer.

• 

A Battery Shutdown signal will not cause an immediate shutdown. it will start a 2-minute shutdown timer. This 

timer cannot be stopped once triggered. if the mains power returns during this countdown, the UPS will still shut 

down and must remain shut down for 10 seconds. Whether the UPS turns back on when the power is restored 

depends on the Auto restart setting.

9.2.3 On Battery

On Battery signal is a normally Open (nO) dry contact. When the UPS is supplying output power from the battery this dry 

contact will be closed. 

9.2.4 Low Battery

Low Battery signal is a normally Open (nO) dry contact. When the UPS is supplying output power from the battery and 

has reached the Low Battery Warning time selected in the configuration program, this dry contact will be closed.

The dry contact rated values for the On Battery and Low Battery signals are: 

• 

rated voltage: 5 V dc; rated current: 30 mA

• 

Working voltage range: 4.5–10 V dc

Summary of Contents for S4K5U6K5C

Page 1: ...S4KC Series Industrial On line UPS 230 V 6000 VA User Manual...

Page 2: ...liability for damages resulting from use of this information or for any errors or omissions The SolaHD and Emerson logos are registered in the U S Patent and Trademark Office All other product or ser...

Page 3: ...0 System Description 10 2 1 Surge Protection Devices EMI RFI Filters 10 2 2 Rectifier Power Factor Correction Circuit 10 2 3 Inverter 10 2 4 Battery Charger 11 2 5 Dc to Dc Converter 11 2 6 Battery 11...

Page 4: ...Configuration Program 25 6 1 Configuration Program Features 25 6 1 1 What You Will Need 25 7 0 Controls Indicators 26 7 1 On Alarm Silence Manual Battery Test Button 26 7 2 Standby Manual Bypass Butto...

Page 5: ...Power Off 34 10 0 Maintenance 35 10 1 Replacing the Internal Battery Pack 35 10 1 1 Battery Replacement Procedures 35 10 2 Battery Charging 36 10 4 Checking UPS Status 37 10 5 Checking UPS Functions...

Page 6: ...wing precautions Turn off and unplug the UPS before cleaning it Clean the UPS with a soft dry cloth Do not use liquid or aerosol cleaners Never block or insert any objects into the ventilation holes o...

Page 7: ...eir own expense The S4K5U6K5C complies with the requirements of EMC Directive 2004 108 EC and the published technical standards Continued compliance requires installation in accordance with these inst...

Page 8: ...followed by important instructions Ac input Ac output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle Dc voltage Equipment grounding co...

Page 9: ...sine wave power The S4K5U6K5C features a light emitting diode LED display to indicate both load percentage and battery capacity It also provides self diagnostic tests a combination ON Alarm Silence Ma...

Page 10: ...ac power to regulated dc power for use by the inverter while ensuring that the wave shape of the input current used by the UPS is near ideal Extracting this sine wave input current achieves two object...

Page 11: ...e UPS in an ambient temperature of 15 C to 25 C 59 F to 77 F Optional external battery cabinets are available to extend battery backup times For backup times see Table 12 2 7 Dynamic Bypass The UPS pr...

Page 12: ...wer Bezel and Battery Access Door Upper Bezel Figure 2 Front view rack mount and tower configurations External Battery Connector IT Power System Access Cover C13 Output Receptacles C19 Output Power Re...

Page 13: ...4 Internal battery pack features 3 3 Removable Power Distribution Box The UPS is shipped with a power distribution box installed This box contains the UPS input circuit breaker NOTE Hardwire and hard...

Page 14: ...sentative immediately 4 2 What s Included The S4K5U6K5C is shipped with the following items Compact disk with MultiLink Configuration program and User manual electronic version One USB cable 2 m 6 1 2...

Page 15: ...uces ventilation and heat dissipation shortening the service life of the unit Maintain an ambient temperature range of 0 C to 40 C 32 F to 104 F NOTE UPS operation in sustained temperatures outside th...

Page 16: ...e front metal bezel cover b Using the finger grips on the display panel gently pull and rotate 90 degrees clockwise and snap it back into position as shown in Figure 8 Figure 8 Rotate the operation an...

Page 17: ...3 mm 18 32 in deep The weight limit per pair of adjustable rack mounting brackets is 91 kg 200 lb Parts included Two rear bracket members two front bracket members two inner bracket members Sixteen M4...

Page 18: ...me mounting height on all four rack mounting rails M5 screws M5 screws Front rack mounting rails Figure 10 Installing the rear member and front member of each bracket assembly 4 Get eight M4 screws an...

Page 19: ...et Figure 12 Fastening the inner members 6 If available apply a bead of grease 25 mm 1 in long at four places inside the bottom curved tracks of the front members as shown in Figure 13 The grease will...

Page 20: ...ket assemblies If it does not recheck the alignment of the front and rear members from Steps 2 and 3 Insert the UPS into the front members Lift the front and push it into the rack Figure 14 Insert the...

Page 21: ...de rail kit 4 Use the enclosed support bases for the tower option to prevent tip over One additional set of support base extensions ships with each external battery cabinet 5 Put the UPS into Bypass M...

Page 22: ...pass 4 Turn the output and input breakers off 5 Loosen other captive screws until the power distribution box releases 6 Remove the power distribution box from the UPS and set it aside 7 Loosen the scr...

Page 23: ...s Model Maximum Breaker Rating S4K5U6K5C D Type 32 A This UPS is equipped with a manual bypass breaker It passes bypass power directly to the bypass breaker from the input terminal block The input cir...

Page 24: ...mm2 8 AWG 2 26 N m 20 in lb NOTES The installer must provide circuit breaker protection according to local codes The mains disconnect should be within sight of the UPS or have an appropriate lock out...

Page 25: ...ch local voltages Enable Disable Auto Restart Select frequency converter operation with a fixed output frequency of 50 or 60 Hz Set the Low Battery alarm time to a value of 2 to 30 minutes Enable Disa...

Page 26: ...battery test press the On button for at least one second while operating from mains power with no alarm conditions present If only three of the five Battery LEDs illuminate allow the UPS to recharge...

Page 27: ...increments 5 The Battery Level indicators will illuminate as shown in Figure 21 The Battery Level indicators display approximate battery capacity at all times The UPS is equipped with automatic and re...

Page 28: ...ult Ac Input indicator Green On when the mains input power is normal off during mains failure flashing when mains power is outside the specifications Battery indicator Amber On when the battery is sup...

Page 29: ...re used verify that the battery cables are fully inserted in the sockets 5 Place the manual bypass breaker in the BYPASS position 6 Turn on the branch circuit disconnect to apply voltage to the input...

Page 30: ...hut Down the UPS 1 Transfer the UPS to manual bypass by pressing the Standby Manual Bypass button once hold it for about 2 seconds If manual bypass is not available disregard the first step 2 Press th...

Page 31: ...the connectors as shown in Figure 22 3 Reinstall IT power system access cover and screws NOTE When connecting to an IT system the installer must provide a 2 pole upstream circuit breaker Refer to all...

Page 32: ...history log Any Mode Shutdown can be operated locally or remotely Local Any Mode Shutdown can be performed by shorting the Pins in Set 3 Remote Any Mode Shutdown can be performed using a switch connec...

Page 33: ...ctor Battery Mode Shutdown wiring must conform to all national regional and local wiring codes and laws This signal must last for 1 5 seconds or longer A Battery Shutdown signal will not cause an imme...

Page 34: ...can be configured to coordinate shutdown across the network with other computers running MultiLink when you purchase a MultiLink License Kit For more information about the IntelliSlot SNMPWEB Card and...

Page 35: ...appropriate replacement battery pack 10 1 1 Battery Replacement Procedures 1 Gently remove the front metal bezel cover from the UPS 2 Loosen and remove the six screws on the battery door as shown in F...

Page 36: ...ttery packs 9 Reconnect the battery plugs and battery receptacles 10 Gently push the battery wire into the UPS battery compartment 11 Reattach the front battery door with the six screws 12 Reattach th...

Page 37: ...act your local SolaHD representative or SolaHD Technical Support Check whether the battery is discharging When the mains input is normal the battery should not discharge If the UPS is operating in Bat...

Page 38: ...icator Descriptions Indicator Diagnosis Audible Alarm A E On bypass from output overload Half second beep every half second A On bypass due to overtemperature condition 1 second beep every 4 seconds B...

Page 39: ...iptions Condition Alarm Battery discharge Half second beep every 10 seconds Low battery Two half second beeps every 5 seconds UPS fault load on bypass 1 second beep every 4 seconds UPS fault no power...

Page 40: ...is within acceptable limits for the UPS UPS has reduced battery backup time Batteries are not fully charged Keep the UPS plugged in continuously for at least 24 hours to recharge the batteries UPS is...

Page 41: ...Support Fault indicator and Diagnostic A and B indicators are illuminated continuous alarm sounds UPS failure includes dual fan failure single fan failure under certain condi tions and battery charge...

Page 42: ...e Power Distribution Box output ac parameters Factory Default V ac 230 V ac Output Connections S4KPAD2 CEHWMBSC Standard See 3 3 Removable Power Distribution Box Frequency 50 or 60 Hz nominal Wave for...

Page 43: ...Transportation ISTA Procedure 1A Table 8 Operating Temperature Parameters Ambient Temperature Model Number S4K5U6K5C pf 30 C 3 C pf 86 F 5 4 F 0 8 pf pf 40 C 3 C pf 104 F 5 4 F 0 8 pf Table 9 Power Di...

Page 44: ...ated non spillable lead acid Qty x V x Rating 20 x 12 V x 9 0 Ah Battery Mfr Part Number Yuasa REW 45 12 Backup Time See Table 12 Recharge Time 3 hours to 90 capacity after full discharge into 100 loa...

Page 45: ...Unit 43 0 94 8 Shipping 54 0 119 0 Battery parameters Type Valve regulated non spillable lead acid Qty x V 1 x 20 x 12 V Battery Mfr Part Number Yuasa NPH5 12 Backup Time See Table 12 environmental r...

Page 46: ...backup times at different loads 12 1 Auto learning Battery Backup Times As batteries age the estimated backup times may become less accurate The S4K5U6K5C is programmed to learn from a full battery di...

Page 47: ...Warranty 13 1 Product Registration To register your product for updates and information on service and support visit our Web site at http www solahd com support registration htm 13 2 Warranty Informa...

Page 48: ...SolaHD U S 800 377 4384 International 847 268 6000 www solahd com P N A272 226 Rev 1 08 16 10...

Reviews: