2.5.1 Transformer-Free UPS Cable Connection
A junction box is factory-installed on each model of the SolaHD S5KC to ease cable connection� Select the appropriate
input cables according to Table 3 and Table 4 based on the UPS rating and mains frequency; however, it is recommended
that you size the over current protection and wiring for the frame rating to easily allow upgrades to the UPS system�
To connect the cable:
NOTE
Input and output cables must be run in separate conduit before cable connection.
1. Remove the knockouts at the junction box (see
Figure 31
) and pull the cables through them, leaving some slack for
installation�
Figure 31: Knockouts
Table 3: Input cable selection list—60Hz
Maximum System
Rated Load
Input voltage - 200VAC
Input voltage - 208VAC
Input voltage - 240VAC
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
5kVA
27A
50A
26A
50A
23A
50A
10kVA
53A
63A
51A
63A
45A
63A
15kVA
80A
100A
77A
100A
67A
100A
20kVA
106A
125A
102A
125A
90A
125A
The power input and output terminals accept a maximum cable cross-sectional area of 35mm2 (2AWG); the minimum cable
cross-sectional area is 16mm2 (6AWG); the rated torque is 4�52Nm (40 in-lb)�
Use of 90°C copper wire is recommended
Table 4: Input cable selection list—50Hz
Maximum System
Rated Load
Input Voltage - 220VAC
Input Voltage - 230VAC
Input Voltage - 240VAC
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
5kVA
25A
50A
24A
50A
23A
50A
10kVA
49A
63A
47A
63A
45A
63A
15kVA
73A
100A
70A
100A
67A
100A
20kVA
97A
125A
93A
125A
90A
125A
The power input and output terminals accept a maximum cable cross-sectional area of 35mm2 (2AWG); the minimum cable cross- sectional area is
16mm2 (6AWG); the rated torque is 4�52Nm (40 in-lb)�
Use of 90°C copper wire recommended
10-Bay SolaHD S5KC
No Transformer
Output Cable Knockout
Input Cable Knockout
16-Bay SolaHD S5KC
No Transformer
Output Cable Knockout
Input Cable Knockout
26 | 2�0
INSTALLATION
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com