NOTICE
Risk of improper installation� Can cause unintended UPS shutdown and loss of power to the load�
Run signal cables separately from power cables� Running cables in the same conduit can cause signal noise, possibly
causing the system to shut down�
NOTE
A jumper is factory-installed between Pins 9 and 10 to disable the Main Control Switch. This will prevent the UPS from being
started accidentally during shipment and installation. This jumper must be removed before the unit can be started.
If the installation does not require connection to a REPO system, the factory-installed jumper must be removed�
3.4 Long Run Time (LRT) Battery Temperature Probe Terminals
The SolaHD S5KC contains a temperature-compensated battery charging system� To use this feature with external LRT
battery systems, Pins 13-16 of the contact terminal strip are used to connect a temperature sensor� See
Figure 49
and
Table 16
for the pin definition of the temperature sensor terminals�
Figure 49: Pin layout of the temperature sensor terminal
3.5 USB Port
The SolaHD S5KC UPS contains a standard B type USB port on the rear of the unit to connect the UPS to a network server
or other computer for monitoring using any operating system, built-in UPS support or in conjunction with MultiLink®
software�
14
13
15
16
Table 16: Pin Definition of the Temperature Sensor Terminal
Position
Name
Description
13
Inside Battery Temperature
Locate battery temperature signal close to the UPS
14
Battery Tempe12V
Battery temperature signal power supply
15
Outside Battery Temperature
Locate battery temperature signal at UPS remote end
16
GND
GND