Menu Window and Data Window
The menu window shows the menu name and allows navigation to different menu items� Each menu item has a set of
data that is displayed in the data window� Using the menu window, you can browse the relevant parameters of the UPS
and can adjust/set some operational parameters� See
Table 22
for the menu and data descriptions�
Table 22: Item Description of Menu Window and Data Window
Menu Name
Data Item
Data Description
Mains
L-N Voltage (V)
L-N input voltage
L-N Current (A)
L-N input current
Frequency (Hz)
Input frequency
L-L Voltage (V)
L-L input voltage
kVA
Input apparent power
Power Factor
Input power factor
Battery
Batt Voltage (V)
Battery bus voltage
Batt Current (A)
Battery bus current
Runtime (Min�)
Battery backup time remaining
Batt Capacity (%)
Percentage of battery capacity
Batt State
Charging, discharging or fully charged
Batt String Count
Online battery string count
Batt Temp (°C)
Battery temperature
Discharge Count
Maximum historical discharge count within current battery modules
Discharge Time (H)
Maximum historical discharge time within current battery modules
EBC Count
Number of connected External Battery Cabinets
Output
L-N Voltage (V)
L-N Output Voltage
L-N Current (A)
L-N Output Current
Frequency (Hz)
Output Frequency
Power Factor
Output Power Factor
Line Voltage (V)
L-L Output Voltage (not displayed for single-phase output model)
Load
kVA
Output apparent power
kW
Output active power
Load Level (%)
Output loading, indicated in percentage of the UPS system rated load
Crest Factor
Output current peak value factor
UPS Info
UPS ID
UPS ID
LCD Module
If the module is online, the serial number and software version will be displayed
Bypass Monitor Module
If the module is online, the serial number and software version will be displayed
Bypass Control Module
If the module is online, the serial number and software version will be displayed
Charger Module
If the module is online, the serial number and software version will be displayed
Power Module
If the module is online, the serial number and software version will be displayed
Battery Module
If the module is online, the serial number and software version will be displayed
Redundant State
PM Installed
The number of installed power modules
PM
Whether there are redundant power modules supplying power�
S5KC SERIES USER MANUAL | 47
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com