Figure 71: Pull out a battery module, a power module or a charge module
!
WARNING
Risk of heavy unit falling over. Can cause equipment damage, injury or death.
Read all of the instructions before attempting to move the unit, lift it, remove packaging or prepare the unit for
installation.
The UPS presents a tipping hazard. Do not remove more than one module at a time. Failure to do so may cause
unit to tip over and cause serious injury.
5.3.2 Replacing the User Interface Module
Replace the User Interface Module only while the SolaHD S5KC is turned On (System Enable switch On and input power
available)� If this module is replaced while the UPS is Off, the UPS settings will be reset to factory defaults when the UPS is
powered On with the new User Interface Module installed�
1. Remove the display bezel on top of the frame�
2. Lift up the user interface module, and put it on top of the UPS frame�
3. Disconnect the network cable from the user interface module�
4. Connect the network cable to the new user interface module�
5. Insert the new user interface module into the clips and replace the display bezel�
Step 3A
Step 3B
Step 3C
S5KC SERIES USER MANUAL | 65
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com