Table 28: Rated Input Voltage Range (Unit: VAC)
System Configuration
% UPS Load
Low Limit Value
High Limit Value
Dual-Inverter Configured to 120 or
127 VAC per Phase
>100%
98 ±3�1
139�5 ±3�1
90% ~ 100%
89 ±3�1 ~ 98 ±3�1
70% ~ 90%
74 ±3�1 ~ 89 ±3�1
30% ~ 70%
60�5 ±3�1 ~ 74 ±3�1
<30%
60�5 ±3�1
Dual-Inverter Configured to 100,
110 or 115 VAC per Phase
>100%
84 ±3�1
90% ~ 100%
80 ±3�1 ~ 84 ±3�1
70%~90%
72 ±3�1 ~ 80 ±3�1
40%~70%
60 ±3�1 ~ 72 ±3�1
<40%
60 ±3�1
Single-Inverter Transformer-Based
and Transformer-Free
> 100%
170 ±5
280 ±5
90 ~ 100%
160 ±5 ~ 170 ±5
70 ~ 90%
140 ±5 ~ 160 ±5
50 ~ 70%
120 ±5 ~ 140 ±5
< 50%
120 ±5
Table 29: SolaHD S5KC External Battery Cabinet Specifications
Parameters
SolaHD S5KC EBC
General and Environmental
Conducted and Radiated EMC Levels
IEC/EN/AS 62040-2—Class A, FCC Part 15 (Class A)
Safety Standards
IEC/EN/AS 62040-1:2008, UL 1778 4th Ed and CSA 22�2 No� 107�3
Immunity Standards
IEC/EN/AS 61000-4-2, 3, 4, 5, 6
Transportation
ISTA-1E
Dimensions, WxDxH
17x28x38 in� (440x712x970mm)
Unit Weight
147�7 lb� (67kg)
Shipping Weight
209�4 lb� (95kg)
Environmental
Operating Temperature
32 to 104°F (0 to 40°C)
Storage Temperature
Without battery: -4 to 140°F (-20 to 60°C)
With battery: 5 to 104°F (-15 to 40°C)
Relative Humidity
0 - 95%, non-condensing
Altitude
10,000 ft�(3000m)
Battery Module *
Lead-Acid Batteries (Per String)
12
Backup Time (Full Load), Minutes
See Estimated Battery Run Times, 7�1 through 7�5
* Up to four external battery cabinets can be connected to each UPS frame and each external battery cabinet can be configured with up to seven
strings of batteries�
S5KC SERIES USER MANUAL | 71