8
INSTALLATION
P
REPARATION
1.
Visually inspect the UPS for freight damage. Report damage to the
carrier and your local distributor or Sola/Hevi-Duty representative.
2.
Decide where to place the S4K
2U
UPS. Install the UPS
indoors in a controlled environment, where it cannot be accidentally
turned off. Place it in an area of unrestricted airflow around the unit,
away from water, flammable liquids, gases, corrosives, and
conductive contaminants. Maintain a minimum clearance of 4 inches
(100mm) in the front and rear of the UPS. Maintain an ambient
temperature range of 32°F to 104°F (0°C to 40°C).
3.
The S4K
2U
UPS may be installed in either a tower
configuration or in a rack, depending on available space and use
considerations. Determine the type of installation and follow the
appropriate instructions in either
Tower UPS Installation
or
Rack-Mount UPS Conversion and Installation
.
T
OWER
UPS I
NSTALLATION
When using the S4K
2U
UPS in a tower configuration, use the
included support base (shown below, left) to stabilize the UPS.
If any battery cabinets are added, they will include spacers to
accommodate the additional cabinets (shown below, right).
!
CAUTION
The UPS is heavy (see Specifications section). Take
proper precautions when lifting or moving it.
NOTE
UPS operation in temperatures above 77°F (25°C) reduces
battery life.
Support base
Spacers added to support
base to accommodate
additional battery cabinets