1.
For slide rail installations, first remove the top/side fin. Slide the
top/side fin forward, then lift it up to remove. If desired, install the optional
rack-mount handles that were shipped with the UPS.
Securing hardware and slide rails are sold separately. Contact your
local distributor or Sola/Hevi-Duty representative for these additional
options and any assistance needed.
2.
Unpack the two
rack-
mounting
bracket assemblies
and mounting
hardware.
T
from the rack-mounting kit
(P/N: SRS1832)
assemblies are
interchangeable between
left-hand or right-hand.
Remove the inner member
of each
bracket
assembly as
s
hown
at right by extending it
to its outermost position,
depressing the
retaining
latch
and then pulling
the inner member from the
bracket
assembly.
NOTE
When rack-mounted, the UPS must be supported by a shelf,
brackets or slide rails on each side. The rack-mount handles
WILL NOT support the weight of the UPS. They are used to
move the UPS into and out of the rack.
BYPASS
UPS ON
BATTERY
AC INPU
T
S O L A
S4K Industrial UPS
!
- +
Optional rack mount handles