1
3
E
XTERNAL
B
ATTERY
C
ABINET
I
NSTALLATION
Optional Sola/Hevi-Duty external battery cabinets may be connected to
the UPS to provide additional battery run time. External battery cabinets
are designed to be placed all on one side of the UPS or stacked beneath
the UPS. There is no limit to the number of external battery cabinets that
can be used but each cabinet will increase the battery recharge time.
1.
Visually inspect the external battery cabinet for freight damage. Report
damage to the carrier and your local distributor or
Sola/Hevi-Duty representative.
2.
For slide rail installations, first remove the top/side fin. Top/side fin
slides forward and then lift up to remove. Optional rack-mount
handles are shipped with the external battery cabinet and may be
installed at this time if desired.
3.
Securing hardware and slide rails are sold separately. Please contact
your local distributor or Sola/Hevi-Duty representative for these
additional options and any assistance needed. Fasten the slides into
position with the screws per the instructions included with the slide rails.
4.
Use the enclosed support bases for the
tower option to prevent tip-over. One
additional set of support base
extensions ships with each external
battery cabinet.
5.
Connect the supplied external battery
cabinet cable to the rear of the external
battery cabinet, then to the rear of
the
UPS.
6.
Turn the battery breaker on the rear of
the external battery cabinet “ON”.
7.
The UPS is now equipped with
additional backup battery runtime. For
approximate battery runtimes refer to
the
Battery Run Times
charts in
this
manual.
!
CAUTION
The external battery cabinet(s) are heavy (see
Specifications section). External battery cabinets can
be used in rack-mount or tower configuration. Take
proper precautions when lifting them.
NOTE
You must use the included Configuration Program to program
the UPS for the number of external battery cabinets connected.
Summary of Contents for S4K2U Series
Page 1: ...S S4K2U Industrial Online Series UPS POWER AVAILABILITY 700 3000VA 120V USER MANUAL...