If the configuration program is used with an earlier UPS model (with an earlier 
UPS firmware version) that does not support the modification of these settings,
the Options tab will display a reminder of the factory default settings.  These 
cannot be changed.

UPS I

NTELLIGENT 

 C

OMMUNICATIONS

The S4K2U UPS is equipped with an Intellislot

®

 port to provide advanced 

communication and monitoring options.  

MultiLink

 software continually monitors the UPS and can shut down 

your computer or server in the event of an extended power failure.

MultiLink can also be configured for use without the serial cable when the 
Intellislot SNMP/Web Card is installed in the UPS. Additionally, MultiLink 
can be configured to coordinate shutdown across the network with other 
computers running MultiLink when you purchase a MultiLink License Kit. 
For more information about the Intellislot SNMP/Web Card and MultiLink 
License Kits, visit our web site (www.solaheviduty.com) or contact your 
local distributor or Sola/Hevi-Duty representative.

Several option cards are available for use in the Intellislot port of the S4K 
Industrial UPS. The Intellislot SNMP/Web Card provides SNMP and 
web-based monitoring and control of the UPS across the network.

The Intellislot MultiPort 4 Card allows you to install MultiLink software on 
four computers and coordinate shutdown in the event of a power failure.

The Intellislot Relay Card provides five dry contact relay outputs for 
custom wired applications and delivers support for built-in shutdown for 
AS/400 systems.

!

CAUTION
To maintain safety (SELV) barriers and for 
electromagnetic compatibility, signal cables should be 
segregated and run separate from all other power 
cables, where applicable.

Summary of Contents for S4K2U Series

Page 1: ...S S4K2U Industrial Online Series UPS POWER AVAILABILITY 700 3000VA 120V USER MANUAL...

Page 2: ......

Page 3: ...ON 8 Preparation 8 Tower UPS Installation 8 Rack Mount UPS Conversion and Installation 9 External Battery Cabinet Installation 13 CONTROLS AND INDICATORS 14 ON Alarm Silence Manual Battery Test Button...

Page 4: ...TION PROGRAM 21 S4K2U UPS Configuration Program Abilities 21 What You Will Need 21 MAINTENANCE 22 Battery Replacement 22 Internal Battery Replacement Procedures 23 Fuse Replacement 24 TROUBLESHOOTING...

Page 5: ...mits for a CLASS A DIGITAL DEVICE PURSUANT TO Part 15 of FCC rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept a...

Page 6: ...block or insert any object into the ventilation holes or other openings of the UPS DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS for example electric drills v...

Page 7: ...caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grou...

Page 8: ...usly conditions and regulates its output voltage whether utility power is present or not It supplies connected equipment with clean sinewave power Sensitive electronic equipment operates best from sin...

Page 9: ...newave input current achieves two objectives The utility power is used as efficiently as possible by the UPS The amount of distortion reflected on the utility is reduced This results in cleaner power...

Page 10: ...cid batteries To maintain battery design life operate the UPS in an ambient temperature of 68 F to 77 F 20 C to 25 C Optional external battery cabinets are available to extend battery run times DYNAMI...

Page 11: ...7 S4K2U INDUSTRIAL Online Series UPS REAR VIEW Input Fuse Circuit Breaker AC Input Support Base Output Receptacles External Battery Connector Cooling Fan Intellislot Port DB 9 Communications Port...

Page 12: ...U UPS may be installed in either a tower configuration or in a rack depending on available space and use considerations Determine the type of installation and follow the appropriate instructions in ei...

Page 13: ...g bracket assemblies and mounting hardware Tfrom the rack mounting kit P N SRS1832 assemblies are interchangeable between left hand or right hand Remove the inner member of each bracket assembly as sh...

Page 14: ...4 rack mounting rails CAUTION Re duce risk of tipping the rack enclosure by placing UPS or battery cabinet in the lowest possible rack position 4 Locate eight 8 M4 screws and eight 8 M4 nuts from har...

Page 15: ...ached from Step 5 into bracket assemblies by inserting top and bottom edges of inner members into the top and bottom curved tracks of front members and sliding the equipment into rack see figure in St...

Page 16: ...emove the outer overlay used for tower installation This reveals a horizontally oriented front panel overlay for rack mounting Snap the front bezel back into place 10 Once the UPS is installed in the...

Page 17: ...e contact your local distributor or Sola Hevi Duty representative for these additional options and any assistance needed Fasten the slides into position with the screws per the instructions included w...

Page 18: ...t of additional problems Manual Battery Test To initiate a manual battery test press the ON button for at least one second while operating from utility power with no alarm conditions present If only t...

Page 19: ...ed a problem Also one or more of the load battery level indicators may be illuminated refer to Troubleshooting section Bypass Indicator LED Amber The Bypass indicator LED is illuminated when the UPS i...

Page 20: ...rovided with the UPS The settings to choose from are 100 110 115 120 and 127 VAC output The factory default setting is 120 VAC CAUTION Never change the voltage settings while the UPS is ON and powerin...

Page 21: ...ing battery mode an alarm sounds every 10 seconds This will change to two beeps every 5 seconds when battery runs low approximately 2 minutes remaining but this is user configurable The AC Input LED w...

Page 22: ...a Hevi Duty s contact closure cable It cannot be used with just a contact closure unless the relay is used to switch a voltage source A 5 12 VDC signal for 1 5 seconds or greater is required to signal...

Page 23: ...onnector is used for Any Mode Shutdown of the UPS output This control input may be used in special applications to disable the UPS output power both Inverter and Bypass The Options tab allows the beha...

Page 24: ...omputers running MultiLink when you purchase a MultiLink License Kit For more information about the Intellislot SNMP Web Card and MultiLink License Kits visit our web site www solaheviduty com or cont...

Page 25: ...Set the Auto Battery test to 7 14 21 or 28 days Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculations reported by Sola Hevi Duty software M...

Page 26: ...ety cautions before proceeding Contact your local distributor or Sola Hevi Duty representative to obtain the appropriate replacement battery kit part number and pricing BATTERY REPLACEMENT CAUTION A b...

Page 27: ...ey are the same If so proceed with Step 6 otherwise STOP and contact your local distributor Sola Hevi Duty representative or Sola Hevi Duty Technical Support Group 6 Line up and slide in the new repla...

Page 28: ...fuse holder and reinstall assembly into the UPS Twist by hand rotate clockwise until fuse holder locks into position 4 Reconnect the input power cord to input AC supply 5 Restart the UPS The UPS is r...

Page 29: ...beep every 4 sec B LED On bypass due to DC bus overvoltage beep every 4 sec C LED On bypass due to control power supply failure beep every 4 sec D LED On bypass due to PFC failure beep every 4 sec E L...

Page 30: ...all receptacle UPS input protection fuse has blown opened UPS is operating from battery mode Save data and close applications Replace UPS input fuse then restart UPS Utility voltage out of UPS input r...

Page 31: ...and Bypass indicator LEDs and diagnostic LED D are illuminated UPS PFC Power Factor Correction Circuit fault UPS requires service Contact your local distributor Sola Hevi Duty representative or Sola H...

Page 32: ...onnections completely power down and restart UPS NOTE If the battery circuit opens while the UPS is running it will be detected when the next battery test is performed Bypass LED is flashing Bypass vo...

Page 33: ...ime remaining Output overload bypass One short beep every half second Overtemperature bypass A one second beep every 4 seconds DC Bus Overvoltage bypass A one second beep every 4 seconds Control power...

Page 34: ...5 plug 10 ft attached w NEMA 5 15 plug OUTPUT AC PARAMETERS Output Receptacles 4 NEMA 5 15R Voltage 100 110 115 120 127 user configurable VAC 3 Frequency 50 Hz or 60 Hz Waveform Sinewave Main Mode Ove...

Page 35: ...30R on 12 in cord Voltage 100 110 115 120 127 user configurable VAC 3 Frequency 50 Hz or 60 Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer to bypass BATTERY...

Page 36: ...able flame retardant lead acid Qty x V x Rating 2 x 4 x 12V x 7 0 or 7 2 AH 2 x 6 x 12V x 9 0 AH Battery Mfg Part China Storage Battery CSBFR 1270 F2 Panasonic UP VW1245P1 Yuasa REW 45 12 FR Back up T...

Page 37: ...384 304 182 240 40 464 272 224 133 168 50 352 200 160 98 128 60 280 152 120 84 88 70 232 128 96 70 72 80 192 104 80 56 64 90 160 96 64 49 56 100 136 88 56 42 40 Internal Battery 3 External Battery Ca...

Page 38: ...his will register your product with Sola Hevi Duty Warranty Information Please see enclosed Terms Conditions and Sales Policies Procedures Software Information Updates for MultiLink software is availa...

Page 39: ......

Page 40: ...this information or for any errors or omissions 2007 Sola Hevi Duty All rights reserved WKURXJKRXW WKH ZRUOG 6SHFL FDWLRQV VXEMHFW WR change without notice Sola Hevi Duty name and logo are registered...

Reviews: