21
CONFIGURATION PROGRAM
This is a new feature included with the new S4K2U UPS line. Several UPS
settings that were previously not available or required custom manufacturing
may now be modified using this program. For most users, the factory default
settings will be adequate. This manual illustrates the features available for
modification, as well as the factory default setting.
S4K2U UPS C
ONFIGURATION
P
ROGRAM
A
BILITIES
•
Select one of five output voltages to match voltages found around
the world.
•
Enable/Disable Auto-Restart.
•
Enable/Disable the Line-Neutral-Reversal/Loss-of-Ground
receptacle wiring alarm.
•
Select frequency converter operation with a fixed output frequency
of 50 or 60 Hz.
•
Set the Low Battery Warning alarm time from 2 to 30 minutes.
•
Enable/Disable the Auto-Battery test.
•
Set the Auto-Battery test to 7, 14, 21, or 28 days.
•
Select the number of external battery cabinets connected to the
UPS to adjust the remaining run time calculations reported by
Sola/Hevi-Duty software.
•
Modify the shutdown setting of DB-9 pin 6 (for information on pin
assignments, see
Communications
on page 18).
What You Will Need
In addition to the S4K 2U UPS, you will need the S4K Configuration Program CD
and serial cable (Beige or Tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3,
5-5) included in the UPS accessory box. The BLACK ML9P9S CONTACT
CLOSURE communication cable IS NOT compatible with the configuration
program. A Windows 95® , 98® , or NT® computer—desktop or laptop—is also
required to set up and run the configuration program.
Refer to“
S4K Configuration Program
” manual (PDF file within
S4K Configuration
CD
) for installing and configuring program.
NOTE
This program is compatible with UPS models beginning with
“S4K”, as in “S4K2U1500.” It is not compatible with earlier
versions of S4000 UPS.