3
2
BATTERY CABINET SPECIFICATIONS
Model Number
S4K2U48BAT
S4K2U96BAT
Used w/ UPS Model
S4K2U700
S4K2U1000
S4K2U1500
S4K2U2000
S4K2U3000
DIMENSIONS in (mm)
Unit
W x D x H
3.5 x 21.5 x 17
(87 x 547 x 430)
3.5 x 24.2 x 17
(87 x 618 x 430)
Shipping
W x D x H
10.5 x 27.2 x 23
(268 x 692 x 585)
10.5 x 27.2 x 23
(268 x 692 x 585)
WEIGHT lbs (kg)
Unit
65.0 (29.5)
93.6 (42.5)
Shipping
71.1 (32.3)
102.5 (46.5)
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, flame retardant, lead acid
Qty x V x Rating
2 x 4 x 12V x 7.0 or 7.2 AH
2 x 6 x 12V x 9.0 AH
Battery Mfg / Part #
China Storage Battery /
CSBFR 1270 F2
Panasonic / UP-VW1245P1
Yuasa / REW 45-12 FR
Back-up Time
See
Battery Run Times
charts
ENVIRONMENTAL
Operating Temp
+32°F to +104°F (0°C to +40°C)
Storage Temp
+5°F to +122°F (-15°C to +50°C)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation
50,000 ft. (15,000 m) maximum
AGENCY
Safety
UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI
FCC Part 15, Subpart B, Class A
Transportation
ISTA Procedure 1A
Summary of Contents for S4K2U Series