3

3

BATTERY RUN TIMES

Load%

700VA

1000VA

1500VA

2000VA

3000VA

Internal 
Battery
(minutes)

10%

248

191

144

56

91

20%

115

87

53

33

46

30%

79

48

38

26

30

40%

58

34

28

19

21

50%

44

25

20

14

16

60%

35

19

15

12

11

70%

29

16

12

10

9

80%

24

13

10

8

8

90%

20

12

8

7

7

100%

17

11

7

6

5

Internal Battery 
+ 1 External 
Battery Cabinet
(minutes)

10%

992

764

576

168

364

20%

460

348

212

99

184

30%

316

192

152

78

120

40%

232

136

112

57

84

50%

176

100

80

42

64

60%

140

76

60

36

44

70%

116

64

48

30

36

80%

96

52

40

24

32

90%

80

48

32

21

28

100%

68

44

28

18

20

Internal Battery 
+ 2 External 
Battery Cabinets
(minutes)

10%

1984

1528

1152

392

728

20%

920

696

424

231

368

30%

632

384

304

182

240

40%

464

272

224

133

168

50%

352

200

160

98

128

60%

280

152

120

84

88

70%

232

128

96

70

72

80%

192

104

80

56

64

90%

160

96

64

49

56

100%

136

88

56

42

40

Internal Battery 
+ 3 External 
Battery Cabinets
(minutes)

10%

2976

2292

1728

560

1092

20%

1380

1044

636

330

552

30%

948

576

456

260

360

40%

696

408

336

190

252

50%

528

300

240

140

192

60%

420

228

180

120

132

70%

348

192

144

100

108

80%

288

156

120

80

96

90%

240

144

96

70

84

100%

204

132

84

60

60

Internal Battery 
+ 4 External 
Battery Cabinets
(minutes)

10%

3968

3056

2304

840

1456

20%

1840

1392

848

495

736

30%

1264

768

608

390

480

40%

928

544

448

285

336

50%

704

400

320

210

256

60%

560

304

240

180

176

70%

464

256

192

150

144

80%

384

208

160

120

128

90%

320

192

128

105

112

100%

272

176

112

90

80

Approximate discharge times are in minutes and at 77°F (25°C) and with a 100% resistive load.

Summary of Contents for S4K2U Series

Page 1: ...S S4K2U Industrial Online Series UPS POWER AVAILABILITY 700 3000VA 120V USER MANUAL...

Page 2: ......

Page 3: ...ON 8 Preparation 8 Tower UPS Installation 8 Rack Mount UPS Conversion and Installation 9 External Battery Cabinet Installation 13 CONTROLS AND INDICATORS 14 ON Alarm Silence Manual Battery Test Button...

Page 4: ...TION PROGRAM 21 S4K2U UPS Configuration Program Abilities 21 What You Will Need 21 MAINTENANCE 22 Battery Replacement 22 Internal Battery Replacement Procedures 23 Fuse Replacement 24 TROUBLESHOOTING...

Page 5: ...mits for a CLASS A DIGITAL DEVICE PURSUANT TO Part 15 of FCC rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept a...

Page 6: ...block or insert any object into the ventilation holes or other openings of the UPS DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS for example electric drills v...

Page 7: ...caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grou...

Page 8: ...usly conditions and regulates its output voltage whether utility power is present or not It supplies connected equipment with clean sinewave power Sensitive electronic equipment operates best from sin...

Page 9: ...newave input current achieves two objectives The utility power is used as efficiently as possible by the UPS The amount of distortion reflected on the utility is reduced This results in cleaner power...

Page 10: ...cid batteries To maintain battery design life operate the UPS in an ambient temperature of 68 F to 77 F 20 C to 25 C Optional external battery cabinets are available to extend battery run times DYNAMI...

Page 11: ...7 S4K2U INDUSTRIAL Online Series UPS REAR VIEW Input Fuse Circuit Breaker AC Input Support Base Output Receptacles External Battery Connector Cooling Fan Intellislot Port DB 9 Communications Port...

Page 12: ...U UPS may be installed in either a tower configuration or in a rack depending on available space and use considerations Determine the type of installation and follow the appropriate instructions in ei...

Page 13: ...g bracket assemblies and mounting hardware Tfrom the rack mounting kit P N SRS1832 assemblies are interchangeable between left hand or right hand Remove the inner member of each bracket assembly as sh...

Page 14: ...4 rack mounting rails CAUTION Re duce risk of tipping the rack enclosure by placing UPS or battery cabinet in the lowest possible rack position 4 Locate eight 8 M4 screws and eight 8 M4 nuts from har...

Page 15: ...ached from Step 5 into bracket assemblies by inserting top and bottom edges of inner members into the top and bottom curved tracks of front members and sliding the equipment into rack see figure in St...

Page 16: ...emove the outer overlay used for tower installation This reveals a horizontally oriented front panel overlay for rack mounting Snap the front bezel back into place 10 Once the UPS is installed in the...

Page 17: ...e contact your local distributor or Sola Hevi Duty representative for these additional options and any assistance needed Fasten the slides into position with the screws per the instructions included w...

Page 18: ...t of additional problems Manual Battery Test To initiate a manual battery test press the ON button for at least one second while operating from utility power with no alarm conditions present If only t...

Page 19: ...ed a problem Also one or more of the load battery level indicators may be illuminated refer to Troubleshooting section Bypass Indicator LED Amber The Bypass indicator LED is illuminated when the UPS i...

Page 20: ...rovided with the UPS The settings to choose from are 100 110 115 120 and 127 VAC output The factory default setting is 120 VAC CAUTION Never change the voltage settings while the UPS is ON and powerin...

Page 21: ...ing battery mode an alarm sounds every 10 seconds This will change to two beeps every 5 seconds when battery runs low approximately 2 minutes remaining but this is user configurable The AC Input LED w...

Page 22: ...a Hevi Duty s contact closure cable It cannot be used with just a contact closure unless the relay is used to switch a voltage source A 5 12 VDC signal for 1 5 seconds or greater is required to signal...

Page 23: ...onnector is used for Any Mode Shutdown of the UPS output This control input may be used in special applications to disable the UPS output power both Inverter and Bypass The Options tab allows the beha...

Page 24: ...omputers running MultiLink when you purchase a MultiLink License Kit For more information about the Intellislot SNMP Web Card and MultiLink License Kits visit our web site www solaheviduty com or cont...

Page 25: ...Set the Auto Battery test to 7 14 21 or 28 days Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculations reported by Sola Hevi Duty software M...

Page 26: ...ety cautions before proceeding Contact your local distributor or Sola Hevi Duty representative to obtain the appropriate replacement battery kit part number and pricing BATTERY REPLACEMENT CAUTION A b...

Page 27: ...ey are the same If so proceed with Step 6 otherwise STOP and contact your local distributor Sola Hevi Duty representative or Sola Hevi Duty Technical Support Group 6 Line up and slide in the new repla...

Page 28: ...fuse holder and reinstall assembly into the UPS Twist by hand rotate clockwise until fuse holder locks into position 4 Reconnect the input power cord to input AC supply 5 Restart the UPS The UPS is r...

Page 29: ...beep every 4 sec B LED On bypass due to DC bus overvoltage beep every 4 sec C LED On bypass due to control power supply failure beep every 4 sec D LED On bypass due to PFC failure beep every 4 sec E L...

Page 30: ...all receptacle UPS input protection fuse has blown opened UPS is operating from battery mode Save data and close applications Replace UPS input fuse then restart UPS Utility voltage out of UPS input r...

Page 31: ...and Bypass indicator LEDs and diagnostic LED D are illuminated UPS PFC Power Factor Correction Circuit fault UPS requires service Contact your local distributor Sola Hevi Duty representative or Sola H...

Page 32: ...onnections completely power down and restart UPS NOTE If the battery circuit opens while the UPS is running it will be detected when the next battery test is performed Bypass LED is flashing Bypass vo...

Page 33: ...ime remaining Output overload bypass One short beep every half second Overtemperature bypass A one second beep every 4 seconds DC Bus Overvoltage bypass A one second beep every 4 seconds Control power...

Page 34: ...5 plug 10 ft attached w NEMA 5 15 plug OUTPUT AC PARAMETERS Output Receptacles 4 NEMA 5 15R Voltage 100 110 115 120 127 user configurable VAC 3 Frequency 50 Hz or 60 Hz Waveform Sinewave Main Mode Ove...

Page 35: ...30R on 12 in cord Voltage 100 110 115 120 127 user configurable VAC 3 Frequency 50 Hz or 60 Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer to bypass BATTERY...

Page 36: ...able flame retardant lead acid Qty x V x Rating 2 x 4 x 12V x 7 0 or 7 2 AH 2 x 6 x 12V x 9 0 AH Battery Mfg Part China Storage Battery CSBFR 1270 F2 Panasonic UP VW1245P1 Yuasa REW 45 12 FR Back up T...

Page 37: ...384 304 182 240 40 464 272 224 133 168 50 352 200 160 98 128 60 280 152 120 84 88 70 232 128 96 70 72 80 192 104 80 56 64 90 160 96 64 49 56 100 136 88 56 42 40 Internal Battery 3 External Battery Ca...

Page 38: ...his will register your product with Sola Hevi Duty Warranty Information Please see enclosed Terms Conditions and Sales Policies Procedures Software Information Updates for MultiLink software is availa...

Page 39: ......

Page 40: ...this information or for any errors or omissions 2007 Sola Hevi Duty All rights reserved WKURXJKRXW WKH ZRUOG 6SHFL FDWLRQV VXEMHFW WR change without notice Sola Hevi Duty name and logo are registered...

Reviews: