Troubleshooting
39
Using the configuration program, the user may specify the number of S4K4U6000 external battery
cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 7
shows estimated run times at different loads.
Table 7
Battery run times
Battery/External Cabinets
Load%
6000VA Run Time
in Minutes
Internal Battery
10%
75
20%
38
30%
25
40%
18
50%
14
60%
11
70%
9
80%
7
90%
6
100%
5
Internal B 1 External
Battery Cabinet
10%
156
20%
90
30%
62
40%
44
50%
34
60%
28
70%
23
80%
19
90%
16
100%
14
Internal B 2 External
Battery Cabinets
10%
235
20%
137
30%
99
40%
74
50%
58
60%
47
70%
39
80%
33
90%
28
100%
25
Internal B 3 External
Battery Cabinets
10%
313
20%
183
30%
133
40%
103
50%
82
60%
67
70%
55
80%
47
90%
41
100%
36
Internal B 4 External
Battery Cabinets
10%
391
20%
229
30%
166
40%
129
50%
105
60%
87
70%
73
80%
63
90%
54
100%
47