i
nstallation and Configuration
6.0 i
nStallation
and
c
onfiGuration
This section includes instructions on how to install, configure and perform initial electrical checks of your
UPS installation.
DO NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so
in
7.0 - Initial Startup and Electrical Checks
.
Visually inspect the UPS for freight damage. Report damage to the carrier and your local distributor or
Sola/Hevi-Duty representative.
CaUTION
The UPS is heavy (see
14.0 - Specifications
). Take proper precautions when lifting or moving it.
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area
of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives and other
conductive contaminants. Maintain a minimum clearance of 4” (100mm) in the front and rear of the UPS. Maintain
an ambient temperature range of 32°F to 104°F (0°C to 40°C).
6.1 Install the Main Cabinet
The S4K6U10000 may be installed either as a tower unit or in a rack, depending on available space and use
considerations. Determine the type of installation and follow the appropriate instructions in either
6.1.1- Tower
UpS Installation or 6.1.2- Installing the adjustable Rack-Mount Kit—Sold Separately
.
6.1.1 Tower UpS Installation
When using the S4K6U10000 in a tower configuration, use the included support base (shown below, left) to
stabilize the UPS.
If any external battery cabinets are added, they will include spacers to accommodate the additional cabinets
(shown in
Section 6.2
).
NOTE
UPS operation in sustained temperatures above 77°F (25°C) reduces battery life.
10
Figure 5
Support base and spacers
End Bases
Spacers
attach Bezels to Top
When used as a tower, the S4K6U10000 requires bezels attached to the top. To connect the bezels:
1. Position the UPS so that the battery compartments are on the right side.
2. Attach the top bezels by placing them on the mounting holes and sliding them toward the rear of the UPS.
Summary of Contents for S4K6U10000
Page 1: ...S S4K6U10000 power availability On Line UPS 120 208V 120 240V USER MANUAL...
Page 2: ......
Page 46: ......
Page 47: ......