i
nstallation and Configuration
6.1.2 Installing the adjustable Rack-Mount Kit—Sold Separately
This kit contains parts needed to mount several different models of UPS and external battery cabinets into
EIA310-D standard four-post racks that are 18-32” deep (457-813mm). The weight limit per pair of adjustable
rack-mounting brackets is 270 pounds (123 kg).
Sola/Hevi-Duty rack-mount bracket kit, part # SRS1832, includes:
Item
Quantity
Rear bracket members
2
Front bracket members
2
Inner bracket members
2
M4 x 8mm machine screws
16
M4 locking hex nuts
8
M5 x 16 mm machine screws
12
Grease packet.
1
Tools needed for installation are:
• one Phillips screwdriver
• one 7mm wrench
The adjustable rack-mounting brackets feature retaining latches to prevent users from inadvertently sliding the
UPS or battery cabinet out of the rack.
To install the rack mount brackets:
1. Unpack two (2) rack-mounting bracket assemblies and mounting
hardware from this kit. Bracket assemblies are interchangeable
between left-hand or right-hand. Remove inner member of each
bracket assembly as shown in at right by extending it to its
outermost position, depressing the retaining latch and then pulling
the inner member out of the bracket assembly.
2. Determine the height position inside the rack enclosure where
you want to mount the UPS or battery cabinet.
3. Install the rear member of each bracket assembly into rack
enclosure with two (2) M5 screws provided in this kit (see figure at
right). The return flanges on the bracket assembly fit to the inside
of rack mounting rails. Insert screws loosely (finger-tight) into the
top and bottom holes of the return flange on the rear member.
Extend the bracket assembly by sliding the front member
forward until it touches the front rack mounting rail. Insert two (2)
M5 screws loosely (finger-tight) into top and bottom holes of the
return flange on each front member. Make sure bracket
assemblies are at the same mounting height on all four (4) rack
mounting rails.
Retaining
Latches
Return
Flanges
Inner
Members
Front
Members
M5 Screws
Front Rack
Mounting Rails
M5 Screws
Rear Rack
Mounting Rails
CaUTION
Reduce the risk of tipping the rack enclosure by placing
the UPS or battery cabinet in the lowest possible
rack position.
11