SOLA 610 UPS Installation
Your UPS should be in a controlled environment. A controlled
environment is one that is indoor, temperature-controlled and free of
conductive or semi-conductive contaminants.
The SOLA 610 is
intended for indoor use only.
There should be adequate ventilation and
the location should be free of dust and fumes. Do not install the unit next
to open windows where uncontrolled environmental conditions could
affect the unit. Do not install the unit in any type of enclosure without first
calling SOLA Technical Support. The unit must have unrestricted air flow.
CAUTION
The environmental specifications shown in Table 1
(below) show the temperature and humidity limits of
the UPS. Do not exceed these limits.
2.6 UPS Locations
ENVIRONMENTAL SPECIFICATIONS
Ambient Operating
< 1500 m
0
o
C to 40
o
C (32
o
F to 104
o
F)
Temperature
1500 - 3000 m
10
o
C to 35
o
C
Ambient Storage
All Models:
-15
o
C to 40
o
C (5
o
F to 104
o
F)
Humidity
All Models:
20% to 95%, non condensing
Altitude
All Models:
8,000 feet (2500M) max.
To optimise the performance of your UPS we recommend you
ensure the battery is fully charged before you use the UPS to
support your critical load.
To recharge the battery, have your electrical contractor install
the UPS wiring to the hardwiring connections, as shown.
When power is supplied to the UPS (without operating any front
panel switches), the UPS will go through a short test sequence,
and the cooling fan will start.
On the front panel the line indicator and the bypass indicator will
illuminate. At this time there is power available at the output
terminals if the output circuit breaker is closed.
Table 1
2.7 Recharging the UPS Battery
!
3
Input
Circuit
Breaker
External
Battery Option
Connection
Output
Circuit
Breaker
Input
Terminals
Output
Terminals