SOLA 610 UPS Optional Features
4.3 Operating CheckUPS II® (cont.)
UPS Control Options
UPS control options are special commands sent to
the UPS. These commands are dependent on the
model of UPS. To display the Additional UPS Control
Options window, select the menu option:
UPS
Control|Control Options…
To send a command to the UPS, click on a
command in the
Control Commands
list box, and
select
Execute Command
. If the control command
requires data to be sent with the command, a data
entry window will appear.
Control Commands
vary
for different UPS models.
When you are finished sending commands to the
UPS, click the
Exit
command button to close the window.
You may wish to have additional output alarms or interface with
an IBM AS400® unit. In this situation, you will need to purchase
an additional alarm card option (Part No. 0610-AS400) which
will install in the communications slot on the rear of the UPS.
The AS400® card option is fitted with two (2) connectors, one
DB9 female and one ES 2 pin. The output available from these
connectors is as follows:-
Output 1 (DB9 female connector)
4.4 Installation and Operation of the AS400® card option
P in. No.
S i g n a l N a m e
D e finition
I/O
C o m m e n ts
1
U P S F a i l
N o r m a l l y o p e n , A c t i v e w i l l c l o s e
O
R e la y c o n t a c t
2
S u m m a r y A l a r m
N o r m a l l y o p e n , A c t i v e w i l l c l o s e .
A c t i v e w h e n U P S f a i l s , b y p a s s
activated, Utility input failure and
lo w b a ttery status
O
R e la y c o n t a c t
3
R e m o te S h u t d o w n ( - )
Ground
4
R e m o te S h u t d o w n ( + )
A c t i v a t e d b y + 5 ~ 1 2 V f o r 1 s e c
duration
I
5
C o m m o n
C o m m o n c o n n e c t i o n f o r P i n s
1 ,2 ,6 ,7 ,8 & 9
R e la y c o m m o n
6
B y p a s s
N o r m a l l y o p e n . W i l l c l o s e w h e n
U P S i s i n B y p a s s M o d e .
O
R e la y c o n t a c t
7
B a ttery low
N o r m a l l y o p e n . W i l l c l o s e w h e n
b a tte r y i s a l m o s t f u l l y d i s c h a r g e d .
O
R e la y c o n t a c t
8
U P S - ON
N o r m a l l y o p e n . W i l l c l o s e w h e n
U P S i s o n .
O
R e la y c o n t a c t
9
U tility Line Failure
N o r m a l l y o p e n . W i l l c l o s e w h e n
the A C input fails.
O
R e la y c o n t a c t
25