SOLA 610 UPS Maintenance and Warranty
Input
Input Voltage Range:
240 Volts
+10%, -20%
Input Frequency Range:
50/60 Hz + 5% (Auto Selecting)
Input Current (Nom. Full Load):
6000VA
=
25A
10000VA
=
51A
Connection:
Hardwired
Output
Output Voltage:
240 Volts + 3% Linear Load (208, 220, 230 V
optional - set by rear panel dip switches)
Output Frequency:
Automatic. Conforms to Input (50 or 60 Hz)
Output Frequency Regulation:
+ 0.5% Inverter free running
(Phase locked to input under normal
conditions)
Distortion:
Less than 4% full linear load
Overload Capacity:
> 130% for 1.5 seconds
Connection:
Hardwired
Efficiency
AC to AC Efficiency:
80% minimum (full load @ 0.7 pf, fully
charged batteries)
Battery
Type:
Sealed Maintenance Free 12V/Cell
Battery System Voltage:
240V DC
Runtime (@ 0.8pf):
6kVA
Full Load
= 9 min
Half Load
= 25 min
10kVA
Full Load
= 12 min
Half Load
= 30 min
Bypass
UPS to/from Bypass Transfer Time:
0 msec
Auto-reverse:
Returns to normal mode after overload
condition removed.
Acoustic Noise
Audible noise at 1 metre:
45-50 dBA (model dependent)
Environmental
Operating Temperature:
0
o
C to 40
o
C altitude < 1500 m
10
o
C to 35
o
C altitude 1500 - 3000 m
(NOTE: High temperature decreases
Battery life)
Storage Temperature:
-15
o
C to +45
o
C
Humidity:
20-90% non-condensing
5.4 Model Specifications
“A” Model (Australian Version)
30