13
SOLA Never Stops Innovating
5.4
Communication Port
To establish communication between the UPS and a computer, connect your computer to the UPS
communication port using the supplied communication cable.
When the communication cable is installed, power management software can exchange data with
the UPS. The software polls the UPS for detailed information on the status of the power environ-
ment. If a power emergency occurs, the software initiates the saving of all data and an orderly
shutdown of the equipment.
The pin functions are described in Table 1.
Table 2. Communication Port Pin Assignment
Pin Number
Signal Name
Function
Direction from the
Multi-Port Module
1
Low Batt
Low Battery relay contact
Out
2
RxD
Transmit to external device
Out
3
TxD
Receive from external device
In
RS-232 low
Conditional Power Off: In absence
In
level signal
of AC power, output is turned off
for>0.4
until normal AC power returns
seconds
4
-
No Connection
-
5
GND
Signal Ground
-
6
-
No Connection
-
7
-
No Connection
-
8
AC Fail
AC Fail relay contact
Out
9
Power V (8 to 24 volts DC power)
Out
USB Port
The UPS is also equipped with a USB communication port. Either the DB-9 communication port or
the USB port may be used to monitor the UPS; however, they cannot operate simultaneously.
Refer to the power management software instructions for using the USB port.
5.5
Communication Slot
The SOLA 625 UPS has a communication slot that allows quick installation of the optional
SNMP/Web adapter or future communication interfaces. These interface adapters extend the
capabilities of the SOLA 625 system to provide compatibility with network and remote monitor-
ing/management systems.
5.6
SNMP/Web Adapter
This adapter provides the SOLA 625 system with its own ethernet network connection, allowing it
to be remotely monitored and controlled via industry-standard internet browsers. The HTML inter-
face enables UPS monitoring and management from anywhere on the internet or within your
intranet. In addition, third-party Simple Network Management Protocol (SNMP) software packages
may also be used to communicate remotely with the SOLA 625 system.