SOLA 4000 - Technical Data
JUE 401269
105
FIG. 1.1 - System Data
1 System Data
Technical Data / System Data
Type SOLA 4000
10
15
20
30
40
60
80
100
120
System configuration
On-line (double conversion)
Nominal input voltage
3Ph+N x 380 ÷ 415 V Tolerance: ± 10%
Nominal input frequency
50 / 60 Hz Tolerance: ± 10%
Nominal output voltage
380 / 400 / 415 Vac (adjustable)
Nominal output frequency
50 / 60 Hz
Output voltage distortion (THD) linear load
non linear load at 100% of Pn and C.F. = 3
< 1%
< 4%
Output voltage regulation with load between 0 and
100%
± 1% (balanced or unbalanced)
Output frequency regulation
- synchronisation with mains
- free running
± 0,5 / 1 / 2 Hz (selectable with software)
± 0,01 %
Rated output power, power factor = 0.8 [kVA]
10
15
20
30
40
60
80
100
120
Rated output power, power factor = 1 [kW]
8
12
16
24
32
48
64
80
96
Efficiency
- 50% load [%]
- 100% load [%]
> 88
> 90
> 88
> 90
> 88
> 90
> 88
> 90
> 90
> 91
> 90
> 91
> 90
> 91
> 90
> 91
> 90
> 91
Losses at nominal load, charged battery <= [kW]
0,8
1,2
1,6
2,4
3,2
4,8
6,4
8
9,6
Overload capacity
- Inverter
- Static bypass switch (SSB)
125 % 10 minutes, 150 % 1 minute
2000 % 20 msec, 200 % 1 minute, 150 % continuous
Permissible inverter output voltage variation for
bypass switching
± 10%
Design standards
IEC 146-4, EN50091-1, IEC 950
Insulation test for 60s
2,0 kV
Cabinet protection
IP 20 acc. to IEC 529, IEC 944 (excl. air exit)
Ambient temperature
- operating temperature
- storage temperature
0 .. 40 °C
0 .. 85 °C (excluding battery)
Permissible relative humidity
< 95 % UR (non condensing)
Maximum altitude above sea level at full load
< 2000 m. Higher altitudes require power derating or
increased cooling
RFI suppression
EMC standard satisfied with EN50091-2 (1995) class A -
IEC801-2 - IEC801-3 - IEC801-4
Audible noise level at 1 meter <= (dBA)
58
58
58
58
60
60
61
61
62