SOLA 4000 - Installation and Initial Start-Up
JUE 401265
24
Version 2 SOLA 4000 with Separate Inputs
for Rectifier and Bypass
Input Cables
Type
SOLA
4000
Rect.
cables
[mm²]
Bypass
cables
[mm²]
earth
cable
[mm²]
10
3x10
4x10
16
15
3x10
4x10
16
20
3x16
4x16
16
30
3x25
4x25
25
40
3x25
4x25
25
60
3x35
4x35
25
80
3x50
4x50
50
100
3x70
4x70
50
120
3x120
4x120
70
TAB. 1.2.3 UPS input cables, version 2
Input Fuses
Type
SOLA
4000
Rect.
Fuses
[A]
Bypass Fuses
[A]
10
25
25
15
35
35
20
50
50
30
63
63
40
100
100
60
100
125
80
125
160
100
160
200
120
200
250
TAB. 1.2.4 UPS input fuses, version 2
Output / Battery Cables
Type
SOLA
4000
Battery
cables
[mm²]
Output cables
[mm²]
Max. inv. input
current
(Vdc=320V)
10
2x16
4x10
25
15
2x16
4x10
40
20
2x25
4x16
50
30
2x25
4x35
75
40
2x35
4x25
100
60
2x50
4x35
150
80
2x70
4x50
200
100
2x95
4x70
250
120
2x120
4 x120
300
TAB. 1.2.5 UPS output cables and fuses, version 2