SOLA 4000 - Installation and Initial Start-Up
JUE 401265
38
1.11 Installation of Parallel Systems
Up to a total of 8 units may be installed together in the one parallel
system.
Note:
The installation for each unit must be performed in accord-
ance to the installation of single units as described in the previous
sections. Additionally to this, the outputs must be connected in
parallel as shown in FIG. 1.11.1 or in FIG.1.11.2
Care must be taken with the installation of the bypass line and in
particular, that the cables from the point of common coupling of the
input supply to the terminals 1-L1, 1-L2, 1-L3 (or 4-L1, 4-L2, 4-L3,
4-N if an optional separate bypass input is installed), are of equal
length. Likewise, the output cables from the output terminals (5-L1,
5-L2, 5-L3, 5-N) to the point of common coupling on the load side
must be of equal length.
1 Installation