SOLA 4000 - Operating Panel
4
PANEL SETTINGS
4.1 DIP Switch Settings
With the DIP switches SW1 and SW2 on the CPU/NCP pcb inside
the front door , the operating parameters can be set according to
actual conditions.
Note:
The following settings apply only with the software V2.0 or
later.
DIP Switch SW1
Dip 1
Dip 2
Dip 3
Dip 4
UPS RATING
(KVA)
OFF
OFF
OFF
OFF
10
ON
OFF
OFF
OFF
15
OFF
ON
OFF
OFF
20
ON
ON
OFF
OFF
30
OFF
OFF
ON
OFF
40
ON
OFF
ON
OFF
60
OFF
ON
ON
OFF
80
ON
ON
ON
OFF
100
OFF
OFF
OFF
ON
120
TAB. 4.1 - Setting of SW1 - UPS rating
DIP Switch SW1
Nominal Voltage
DIP 7
DIP 8
Vnom
OFF
OFF
120
ON
OFF
220
OFF
ON
230
ON
ON
240
TAB. 4.2 - Setting of SW1
TAB. 4.3 - Setting of SW1
Nominal Voltage
DIP Switch SW1
DIP 5
CONFIGURATION
OFF
Not Hot-standby
ON
Hot-Standby
DIP 6
BYPASS - LINE
OFF
Installed
ON
Not installed
4 Panel Settings