SOLA 4000 - PCB Description
JUE 401268
95
CPHC16 - R Front View
FIG. 1.2 illustrates the display, switches and connectors of the
CPHC16 - R PCB which are accessible from the front.
- 7 segment display for diagnostics (see table below)
- Reset max. Vdc pushbutton: press when the character "4" is
displayed or the central segment is blinking.
- Reset Boost Charge Alarm
- Reset after EPO (V2.1)
- RS232 connector (male)
- RS485 connector (female)
1 UPS Control Logic
DIAGNOSTICS
RESET MAX. Vdc
RS 232
RS 485
Priority
Indication
Diagnostics
1
8
E²PROM failure
2
2
Fuse blown
3
C
Mains not OK
4
P
Wrong phase rotation
5
3
Overtemperature
6
4
Overvoltage
7
Ø
Pulse release missing
8
9
Rectifier failure
9
6
Fan failure
10
L
Overload
--
Boost charge
"--"
(when blinking)
Has left the boost
charge due to a given
time limit but the
battery was not
completely charged.
Reset with "RESET
max. Vdc" above.