20
EN
G
LI
SH
Table of countries
1)
Country code and name as shown on the display.
2)
Disconnection values are upper and lower deviations from the peak values of
the rated voltage (in%) and the associated
switch-off time (in s).
3)
Disconnection values are upper and lower deviations from the average values of
the rated voltage (in%) and the associated switch-off time (in s).
4)
Disconnection values are upper/lower deviations from the rated frequency (in
Hz) and the switch-off time (in s).
5)
Maximum output power 3330 W.
6)
Maximum output power 2000 W.
7)
For systems smaller than 3 kW maximum power.
8)
For systems between 3 kW and 6 kW maximum power.
Country
Rec
onnec
tion time
nominal v
oltage
Voltage disconnection
values (peak values)
2)
Voltage disconnection
value
ø
(average values)
3)
nominal f
re
qu
en
cy Frequency disconnection
values
4)
Reac
tiv
e po
w
er c
on
trol
upper
lower
upper
lower
upper
lower
Name
Display
1)
s
V
%
s
%
s
%
s
%
s
Hz Hz
s
Hz
s
Australia
6100
Australia
60
230 17.0 2.00
-13
2.00
–
–
–
–
50
5.0
2.0
-5.0
2.0
no
Bulgaria
3590
Bâlgariyes
30
230 15.0 0.20
-20
0.20
10
600
–
–
50
0.2
0.2
-2.5
0.2
no
Belgium 2
3203
Belgique 2
5)
60
230 15.0 0.20
-20
0.20
10
600
–
–
50
1.5
0.2
-2.5
0.2
no
Belgium 2 unlimited
3203
Belgique 2 unl.
60
230 15.0 0.20
-20
0.20
10
600
–
–
50
1.5
0.2
-2.5
0.2
no
Brazil 220
5500
Brasil 220V 60Hz
300 220 10.0 0.20
-20
0.40
–
–
–
–
60
2.0
0.2
-2.5
0.2
yes
Brazil 230
5501
Brasil 230V 60Hz
300 230 10.0 0.20
-20
0.40
–
–
–
–
60
2.0
0.2
-2.5
0.2
yes
Czech Republic
42000
Česko
120 230 15.0 0.20
-15
0.20
10
600
–
–
50
0.5
0.2
-0.5
0.2
no
Cyprus
35700
Cyprus
180 230 10.0 0.50
-10
0.50
–
–
–
–
60
2.0
0.5
-3.0
0.5
yes
Denmark unlimited
4500
Danmark unl.
60
230 15.0 0.20
-20
0.20
10
600
–
–
50
1.5
0.2
-2.5
0.2
yes
Denmark 2
4501
Danmark
6)
60
230 15.0 0.20
-20
0.20
10
600
–
–
50
1.5
0.2
-2.5
0.2
yes
Germany
4900
Deutschland
60
230 15.0 0.20
-20
0.20
10
600
–
–
50
1.5
0.2
-2.5
0.2
yes
Estonia
3720
Eesti
300 230 15.0 0.20
-15
1.50
–
–
–
–
50
1.0
0.5
-3.0
0.5
no
Ireland
35300
Éire
30
230 10.0 0.50
-10
0.50
–
–
–
–
50
0.5
0.5
-2.0
0.5
no
Spain
3400
España 1699
180 230 15.0 0.20
-15
1.50
10
1.5
–
–
50
0.5
0.5
-2.0
3.0
no
France
3300
France
30
230 15.0 0.20
-20
0.20
10
600
–
–
50
0.6
0.2
-2.5
0.2
no
Greek Mainland
3000
Greece continent
180 230 15.0 0.50
-20
0.50
10
600
–
–
50
0.5
0.5
-0.5
0.5
no
Greek Islands
3001
Greece islands
180 230 15.0 0.50
-20
0.50
10
600.
–
–
50
1.0
0.5
-2.5
0.5
no
India
9100
India
300 230 35.0 0.05
-50
0.10
10
2.0
-15
2.0
50
1.0
0.2
-1.0
0.2
no
Israel
9720
Israel
300 230 35.0 0.05
-50
0.10
10
2.0
-15
2.0
50
1.0
2.0
-1.0
2.0
no
Italy 3
3902
Italia 3
30
230 22.0 0.10
-25
0.20
–
–
–
–
50
5.0
0.2
-5.0
0.2
no
Italy 8
3907
Italia 8
7)
300 230 15.0 0.20
-15
0.40
10
600
-15
0.4
50
0.5
0.1
-0.5
0.1
no
Italy 9
3908
Italia 9
8)
300 230 15.0 0.20
-15
0.40
10
600
-15
0.4
50
0.5
0.1
-0.5
0.1
yes
Italy 10
3908
Italia 10
7)
300 230 15.0 0.20
-15
0.40
10
600
-15
0.4
50
0.5
0.1
-2.5
0.1
no
Italy 11
3908
Italia 11
8)
300 230 15.0 0.20
-15
0.40
10
600
-15
0.4
50
0.5
0.1
-2.5
0.1
yes
Costa Rica
5060
Latinoamérica 60Hz
20
240 10.0 0.20
-20
0.20
–
–
–
–
60
0.6
0.2
-0.6
0.2
no
Hungary
3600
Magyarország
300 230 35.0 0.05
-50
0.10
10
2.0
-15
2.0
50
1.0
0.2
-1.0
0.2
no
Malaysia
6000
Malaysia
180 230 17.4 2.00
-13
2.00
–
–
–
–
50
5.0
2.0
-5.0
2.0
no
Mauritius
23000
Mauritius
180 230 10.0 0.20
-6
1.50
6
1.5
–
–
50
1.0
0.5
-3.0
0.5
no
Mexico
5200
Mexico
300 240 35.0 0.05
-50
0.10
10
600
60
1.2
5.0 1.2
5.0
-1.2
5.0
yes
Netherlands
3100
Nederland
30
230 10.0 2.00
-20
2.00
–
–
–
–
50
1.0
2.0
-2.0
2.0
no
Austria
4300
Österreich
30
230 15.0 0.10
-20
0.20
12
600
–
–
50
1.5
0.2
-2.5
0.2
yes
Poland
4800
Polska
30
230 15.0 0.20
-15
1.50
10
600
–
–
50
1.0
0.5
-3.0
0.5
no
Portugal
35100
Portugal
20
230 15.0 0.20
-15
1.50
10
600
–
–
50
1.0
0.5
-3.0
0.5
no
Slovenia
38600
Sloveniyes
30
230 15.0 0.20
-30
0.20
10
1.5
-15
1.5
50
1.0
0.2
-3.0
0.2
no
South Africa
2700
South Africa
60
230 20.0 0.16
-50
0.20
10
2.0
-15
2.0
50
2.0
0.5
-2.5
0.5
no
Switzerland
4100
Suisse
30
230 15.0 0.20
-20
0.20
10
600
–
–
50
0.2
0.2
-2.5
0.2
no
Finland
35800
Suomi
30
230 10.0 0.20
-15
0.20
–
–
–
–
50
1.0
0.2
-2.0
0.2
no
Sweden
4600
Sverige
30
230 15.0 0.20
-15
0.20
11
60
–
–
50
1.0
0.5
-3.0
0.5
no
Tahiti
6890
Tahiti 60Hz
30
230 15.0 0.20
-20
0.20
10
600
–
–
60
2.5
0.2
-5.0
0.2
no
Taiwan 220
8860
Taiwan 220V 60Hz
300 230 10.0 0.20
-12
0.20
–
–
–
–
60
0.5
0.5
-0.5
0.5
no
Thailand MEA
6600
Thailand MEA
300 230 20.0 0.16
-50
0.30
10
1.0
-10
2.0
50
1.0
0.1
-2.0
0.1
no
Thailand PEA
6600
Thailand PEA
150 220 19.0 0.16
-50
0.30 10.2
1.0
-9.4
2.0
50
1.0
0.1
-2.0
0.1
yes
Türkei
9000
Türkiye
30
230 15.0 0.20
-20
0.20
10
600
–
–
50
0.2
0.2
-2.5
0.2
no
United Kingdom
G59/3
4401
United Kingdom
(G59/3)
180 240 19.0 0.50
-20
0.50
14
1.0
-13
2.5
50
2.0
0.5
-3.0
0.5
no
United Kingdom
G83/1
4402
United Kingdom
(G83/1)
20
230 14.7
1.5
-10
1.5
-
-
-
-
50
2.0
0.5
-3.0
0.5
no
United Kingdom
G83/2
4400
United Kingdom
(G83/2)
20
230 19.0 0.50
-20
0.50
14
1.0
-13
2.5
50
2.0
0.5
-3.0
0.5
no
EN 50438 -2014
50438
EN 50438:2014
60
230 15.0 0.20
-15
1.50
10
3.0
–
–
50
2.0
0.5
-2.5
0.5
no
Droop Mode
0007
Droop-Mode 50Hz
60
230 20.0 0.50
-20
0.50
–
–
–
–
50
5.0
0.5
-3.5
0.5
no
Droop Mode 60
0008
Droop-Mode 60Hz
60
230 20.0 0.50
-20
0.50
–
–
–
–
60
5.0
0.5
-3.5
0.5
no
Attention
Danger of yield losses. Activation of the Droop Mode is not permitted in sys-
tems connected to the public electricity grid.
Activation of the Droop Mode is recommended when the inverter is operated
in conjunction with a stand-alone inverter in a system that is not connected to
the public electricity grid.