Turbo 3P1 / 3P2 inverter
Advice
The requirements for the country-specific grid parameters may change at short notice. Contact Solar Frontier technical support if the parameters specified in the table no
longer correspond to the legally prescribed requirements in your country.
Country
Rec
onnec
tion time
nominal v
oltage
Voltage disconnection values
(peak values)
2)
Voltage disconnection
value
ø
(average values)
3)
nominal f
re
-
quenc
y
Frequency disconnection
values
4)
upper
lower
upper
lower
upper
lower
Name
Display
1)
s
V
%
s
%
s
%
s
%
s
Hz
Hz
s
Hz
s
Bulgaria
3590
Bâlgariyes
30
400
15.0
0.20
-20
0.20
10
600
–
–
50
0.2
0.2
-2.5
0.2
Belgium 2 unlimited
3203
Belgique 2 unl.
60
400
15.0
0.20
-20
0.20
10
600
–
–
50
1.5
0.2
-2.5
0.2
Brazil 220
5500
Brasil 220V
300 380
10.0
0.20
-20
0.40
–
–
–
–
60
2.0
0.2
-2.5
0.2
Brazil 230
5501
Brasil 230V
300 400
10.0
0.20
-20
0.40
–
–
–
–
60
2.0
0.2
-2.5
0.2
Czech Republic
42000
Česko
30
400
15.0
0.20
-15
0.20
10
600
–
–
50
0.5
0.2
-0.5
0.2
Cyprus
35700
Cyprus
180 400
10.0
0.50
-10
0.50
–
–
–
–
50
2.0
0.5
-3.0
0.5
Denmark unlimited
4500
Danmark unl.
60
400
15.0
0.20
-20
0.20
10
600
–
–
50
1.5
0.2
-2.5
0.2
Germany
4900
Deutschland
60
400
15.0
0.20
-20
0.20
10
600
–
–
50
1.5
0.2
-2.5
0.2
Droop Mode
0007
Droop-Mode
60
400
20.0
0.50
-20
0.50
–
–
–
–
50
5.0
0.5
-3.5
0.5
Estonia
3720
Eesti
300 400
15.0
0.20
-15
1.50
–
–
–
–
50
1.0
0.5
-3.0
0.5
Ireland
35300
Éire
30
400
10.0
0.50
-10
0.50
–
–
–
–
50
0.5
0.5
-2.0
0.5
EN 50438 :2007
50438
EN 50438:2007
20
400
15.0
0.20
-15
1.50
–
–
–
–
50
1.0
0.5
-3.0
0.5
EN 50438 :2014
50438
EN 50438:2014
20
400
15.0
0.20
-15
1.50
10
3.0
–
–
50
2.0
0.5
-2.5
0.5
Spain
3400
España 1699
180 400
15.0
0.20
-15
1.50
10
1.5
–
–
50
0.5
0.5
-2.0
3.0
France
3300
France
30
400
15.0
0.20
-20
0.20
10
600
50
0.6
0.2
-2.5
0.2
Greek Mainland
3000
Greece continent
180 400
15.0
0.50
-20
0.50
10
600
–
–
50
0.5
0.5
-0.5
0.5
Greek Islands
3001
Greece islands
180 400
15.0
0.50
-20
0.50
10
600
–
–
50
1.0
0.5
-2.5
0.5
India
9100
India
300 400
35.0
0.05
-50
0.10
10
2.0
-15
2.0
50
1.0
0.2
-1.0
0.2
Italy 3
3902
Italia 3
30
400
22.0
0.10
-25
0.20
–
–
–
–
50
5.0
0.2
-5.0
0.2
Malaysia
6000
Malaysia
180 400
17.4
2.00
-13
2.00
–
–
–
–
50
5.0
2.0
-5.0
2.0
Mauritius
23000
Mauritius
180 400
10.0
0.20
-6
1.50
6
1.5
–
–
50
1.0
0.5
-3.0
0.5
Mexico
5200
Mexico
300 415
35.0
0.05
-50
0.10
10
600
-15
600
60
1.2
5.0
-1.2
5.0
Netherlands
3100
Nederland
30
400
10.0
2.00
-20
2.00
–
–
–
–
50
1.0
2.0
-2.0
2.0
Austria
4300
Österreich
30
400
15.0
0.10
-20
0.20
12
600
–
–
50
1.5
0.2
-2.5
0.2
Austria VN
4301
Österreich VN
30
400
15.0
0.10
-20
0.20
12
600
–
–
50
1.5
0.2
-2.5
0.2
Poland
4800
Polska
30
400
15.0
0.20
-15
1.50
10
600
–
–
50
1.0
0.5
-3.0
0.5
Slovenia
38600
Sloveniyes
30
400
15.0
0.20
-30
0.20
10
1.5
-15
1.5
50
1.0
0.2
-3.0
0.2
Switzerland
4100
Suisse
30
400
15.0
0.20
-20
0.20
10
600
–
–
50
0.2
0.2
-2.5
0.2
Finland
35800
Suomi
30
400
10.0
0.20
-15
0.20
–
–
–
–
50
1.0
0.2
-2.0
0.2
Sweden
4600
Sverige
30
400
15.0
0.20
-15
0.20
11
60.0
–
–
50
1.0
0.5
-3.0
0.5
Taiwan 220
8860
Taiwan
30
380
10.0
0.20
-12
0.20
–
–
–
–
60
0.5
0.5
-0.5
0.5
Thailand MEA
6601
Thailand MEA
300 230
50.0
0.30
-35
0.05
14
2.0
-5
2.0
50
1.0
0.1
-0.1
0.1
Thailand PEA
6600
Thailand PEA
300 220
20.0
0.16
-50
0.30
10
1.0
-10
2.0
50
1.0
0.1
-2.0
0.1
Turkey
9000
Türkiye
30
400
15.0
0.20
-20
0.20
10
600
–
–
50
0.2
0.2
-2.5
0.2
Table 6
Table of countries
1)
Country code and name as shown on the display.
2)
Disconnection values are upper and lower deviations from the peak values of
the rated voltage (in %) and the associated switch-off time (in s).
3)
Disconnection values are upper and lower deviations from the average values of
the rated voltage (in %) and the associated switch-off time (in s).
4)
Disconnection values are upper/lower deviations from the rated frequency
(in Hz) and the switch-off time (in s).
Attention
Danger of yield losses. Activation of the Droop Mode is not permitted in systems
connected to the public electricity grid.
Activation of the Droop Mode is recommended when the inverter is operated in
conjunction with a stand-alone inverter in a system that is not connected to the
public electricity grid.