1.  About this Manual

Thank you for choosing Solar Frontier’s (SF) CIS photovoltaic (PV) modules. At Solar Frontier, we look forward to providing you the 
highest standards in solar energy performance and customer service.

The following manual contains vital information on handling, installing, wiring, operating and maintaining SF modules, and the 
associated risks. It is essential that you thoroughly understand all the instructions and warnings in this document, together with any 
information provided by balance of system manufacturers, to ensure the correct and safe use of our modules.  
Please share this manual with the installer/operator and keep it for future reference. BE SURE TO CONFORM TO ALL RELEVANT LOCAL 
AND NATIONAL LAWS, REGULATIONS AND CODES WHEN INSTALLING, WIRING, OPERATING AND MAINTAINING SF MODULES.
For additional queries, please contact your local supplier or Solar Frontier.

2.  General Information

Solar Frontier’s CIS modules generate an electrical direct current when exposed to sunlight. They are designed for terrestrial use. The 
nominal power of SF modules indicates the power generated under Standard Test Conditions (module temperature: 25 °C, air mass 
1.5, solar irradiance 1.000 W/m

2

). SF module power output in actual operating conditions may vary. The amount of electrical direct cur-

rent generated by SF modules is proportional to irradiance intensity, while the voltage is affected by temperature.

3.  Technical Data

The technical data below represents SF modules distributed in all regions.  

Information required by UL is marked accordingly and is only relevant to US installers.

3.1  Electrical Characteristics

Electrical Data at Standard Test Conditions 25 °C, AM1.5, 1.000 W/m

2

 (UL: per ASTM E892)

SF140-S SF145-S SF150-S SF155-S SF160-S SF165-S SF170-S

Nominal power

Pmax

140 W

145 W

150 W

155 W

160  W

165  W

170  W

Power tolerance

+5 W / 0 W

Open circuit voltage

Voc

107.0 V

107.0 V

108.0 V

109.0 V

110.0 V

110.0 V

112.0 V

Short circuit current

Isc

2.10 A

2.20 A

2.20 A

2.20 A

2.20 A

2.20 A

2.20 A

Voltage at nominal power

Vmpp

80.5 V

81.0 V

81.5 V

82.5 V

84.0 V

85.5 V

87.5 V

Current at nominal power

Impp

1.74 A

1.80 A

1.85 A

1.88 A

1.91 A

1.93 A

1.95 A

Open circuit voltage at -10 °C and 1,250 W/m

2

 (UL)

120.0 V

120.0 V

121.0 V

122.0 V

123.0 V

123.0 V

125.0 V

Short circuit current at 75 °C and 1,250 W/m

2

 (UL)

2.64 A

2.76 A

2.76 A

2.76 A

2.76 A

2.76 A

2.76 A

Photovoltaic modules may produce more current and/or voltage under actual operating conditions than in Standard Test Conditions. 
The electrical characteristics are within ±10 % of the indicated Isc and Voc values under STC. The power output stated on the label is 
measured at the plant after module preconditioning. The values of Isc and Voc marked on modules should be multiplied by a factor of 
1.25 to determine component voltage ratings, conductor ampacities, overcurrent device ratings and size of controls connected to the 
module output.

UL:

 Refer to Section 690.8 of the National Electrical Code for an additional multiplying factor of 125 % (80 % derating). Installation must 

be completed in accordance with CSA C22.1, Safety Standard for Electrical Installations, Canadian Electrical Code, Part 1. 

Electrical Data at Nominal Operating Cell Temperature Conditions (NOCT 47 °C)

SF140-S SF145-S  SF150-S  SF155-S SF160-S SF165-S SF170-S

Nominal power

Pmax

104 W

108 W

111 W

115 W

119 W

123 W

126 W

Open circuit voltage

Voc

97.4 V

97.4 V

98.3 V

99.2 V

100.0 V

100.0 V

102.0 V

Short circuit current

Isc

1.68 A

1.76 A

1.76 A

1.76 A

1.76 A

1.76 A

1.76 A

Voltage at nominal power

Vmpp

75.5 V

76.0 V

76.4 V

77.4 V

78.8 V

80.2 V

82.1 V

Current at nominal power

Impp

1.38 A

1.43 A

1.47 A

1.49 A

1.51 A

1.53 A

1.55 A

Summary of Contents for SF140-S

Page 1: ...Solar Frontier Europe GmbH Data Sheet and Installation and Maintenance Manual SF140 S SF145 S SF150 S SF155 S SF160 S SF165 S SF170 S ENGLISH...

Page 2: ...2...

Page 3: ...id from August 2013 It replaces all previous changes made to this document Content 1 About this Manual 4 2 General Information 4 3 Technical Data 4 3 1 Electrical Characteristics 4 3 2 Module Performa...

Page 4: ...SF155 S SF160 S SF165 S SF170 S Nominal power Pmax 140 W 145 W 150 W 155 W 160 W 165 W 170 W Power tolerance 5 W 0 W Open circuit voltage Voc 107 0 V 107 0 V 108 0 V 109 0 V 110 0 V 110 0 V 112 0 V S...

Page 5: ...hould not exceed 7 A under any circumstances UL Modules installed in parallel will be provided with the listed maximum series fuse as specified 3 5 Mechanical Data Dimensions L x W x H 1 257 x 977 x 3...

Page 6: ...5 31 1 225 31 1 225 30 12 13 5 35 35 30 372 5 372 5 454 5 454 5 566 5 598 5 5 934 2 21 5 21 5 548 5 120 35 0 5 977 2 90 444 28 2 568 5 5 Mounting holes 2 x Grounding 2 x 4 4 x 8 5 4 x 6 6 Mounting hol...

Page 7: ...circuit voltage must never exceed the maximum system voltage including in low temperature conditions Leakage currents could create a shock hazard or fire Do not disconnect operational modules or elect...

Page 8: ...temperature range indicated in the module s technical specifications 6 3 Module Handling Instructions Do not disassemble or modify SF modules This may result in an electric shock fire or other accide...

Page 9: ...oduction Modules can be installed horizontally landscape or vertically portrait Maintain a space between SF modules and the roof This will allow air to circulate cooling the module and allowing conden...

Page 10: ...0 Pa 50 lbs ft2 to the front and back of the module UL 1 600 Pa 33 4 lbs ft2 to the front and back of the module 1 5 times the design load is applied to the module during UL testing 2 400 Pa 50 lbs ft...

Page 11: ...inimum TUV 2 400 Pa 50 lbs ft2 to the front and back of the module UL 1 600 Pa 33 4 lbs ft2 to the front and back of the module 1 5 times the design load is applied to the module during UL testing 2 4...

Page 12: ...module overlap min 8 mm 8 mm 3 mm 3 mm 256 mm 75 mm 745 mm 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm 745 mm 256 mm 75 mm 75 mm 75 mm 75 mm Array Installation section Landscape...

Page 13: ...g cautions Be aware of the necessary grounding requirements prior to installation Your local authorities can help you further Install arrestors surge absorbers or any other appropriate lightning prote...

Page 14: ...r Cables drooping from the terminal box are hazardous and must be avoided Cables should be secured so they are not exposed to direct sunlight such as behind the module The sum of Voc of modules in ser...

Page 15: ...ny other hard materials use only soft cloths or sponges for removing dirt from the SF modules surface When replacement parts are required be sure the installer servicer uses parts specified by the man...

Page 16: ...iafilmplatz 8 82031 Gr nwald bei M nchen Germany Tel 49 89 92 86 142 0 Italy Solar Frontier Europe GmbH Sede Secondaria per l Italia Via Domenico Cotugno 49 A scala B 70124 Bari Italy Tel 39 080 90 21...

Reviews: