background image

9

6.4  Module Mounting Instructions

Mounting Structures Cautions 

 • Pay attention to the electrochemical series when selecting support structure material to avoid galvanic corrosion.

 • Fasten and lock bolts completely. Inadequate mounting may result in SF modules falling or other accidents.

 • Ensure that the SF modules are securely fastened to the mounting support structure that is durable, made of corrosive and UV 

resistant material, and follow the applicable local and civil codes.

 • Ensure, that your mounting support structure is designed to withstand the SF modules design snow and wind loads applicable for 

your chosen site. Solar Frontier will not be responsible if the SF modules are damaged due to the durability of the mounting sup-
port structure. Consult your mounting structure manufacturer for an appropriate mounting design.

Mounting the Solar Modules

 • PV modules should typically face South in the Northern Hemisphere and North in the Southern Hemisphere for optimal  

power production.

 • Modules can be installed horizontally (landscape) or vertically (portrait).

 • Maintain a space between SF modules and the roof. This will allow air to circulate, cooling the module, and  

allowing condensation to dissipate. Solar Frontier recommends a distance of at least 100 mm. 

Mounting with Screws

SF modules should be fastened to the support structure using the mounting holes on the frame. The support structure  
should be securely fastened to a non-corrosive roof. Tighten the screws with an adequate torque value. Please refer to further instruc-
tions and adequate torque value provided by the screw manufacturer.

Mounting with Inner Holes

Each module will require four M6 (or 1/4 in) bolts with washers, lock washers and nuts. Tighten the screws with an adequate torque value. 

UL:  

Recommended tightening torque is 8 Nm (70.8 lb in) minimum.

TUV: 2,400 Pa (50 lbs/ft

2

) to the front and back of the module

UL: 1,600 Pa (33.4 lbs/ft

2

) to the front and back of the module

1.5 times the design load is applied to the module during UL testing. 2,400 Pa (50 lbs/ft

2

) is applied to test 1,600 Pa  

(33.4 lbs/ft

2

) UL design load.

Landscape (horizontal)

256 mm ±1 mm 

745 mm 

Portrait (vertical)

Portrait (vertical)

256 mm 

±1

 mm

 

745 mm

 

174 mm 

±1

 mm

 

909 mm

 

909 mm 

174 mm ±1 mm 

Landscape (horizontal)

Summary of Contents for SF140-S

Page 1: ...Solar Frontier Europe GmbH Data Sheet and Installation and Maintenance Manual SF140 S SF145 S SF150 S SF155 S SF160 S SF165 S SF170 S ENGLISH...

Page 2: ...2...

Page 3: ...id from August 2013 It replaces all previous changes made to this document Content 1 About this Manual 4 2 General Information 4 3 Technical Data 4 3 1 Electrical Characteristics 4 3 2 Module Performa...

Page 4: ...SF155 S SF160 S SF165 S SF170 S Nominal power Pmax 140 W 145 W 150 W 155 W 160 W 165 W 170 W Power tolerance 5 W 0 W Open circuit voltage Voc 107 0 V 107 0 V 108 0 V 109 0 V 110 0 V 110 0 V 112 0 V S...

Page 5: ...hould not exceed 7 A under any circumstances UL Modules installed in parallel will be provided with the listed maximum series fuse as specified 3 5 Mechanical Data Dimensions L x W x H 1 257 x 977 x 3...

Page 6: ...5 31 1 225 31 1 225 30 12 13 5 35 35 30 372 5 372 5 454 5 454 5 566 5 598 5 5 934 2 21 5 21 5 548 5 120 35 0 5 977 2 90 444 28 2 568 5 5 Mounting holes 2 x Grounding 2 x 4 4 x 8 5 4 x 6 6 Mounting hol...

Page 7: ...circuit voltage must never exceed the maximum system voltage including in low temperature conditions Leakage currents could create a shock hazard or fire Do not disconnect operational modules or elect...

Page 8: ...temperature range indicated in the module s technical specifications 6 3 Module Handling Instructions Do not disassemble or modify SF modules This may result in an electric shock fire or other accide...

Page 9: ...oduction Modules can be installed horizontally landscape or vertically portrait Maintain a space between SF modules and the roof This will allow air to circulate cooling the module and allowing conden...

Page 10: ...0 Pa 50 lbs ft2 to the front and back of the module UL 1 600 Pa 33 4 lbs ft2 to the front and back of the module 1 5 times the design load is applied to the module during UL testing 2 400 Pa 50 lbs ft...

Page 11: ...inimum TUV 2 400 Pa 50 lbs ft2 to the front and back of the module UL 1 600 Pa 33 4 lbs ft2 to the front and back of the module 1 5 times the design load is applied to the module during UL testing 2 4...

Page 12: ...module overlap min 8 mm 8 mm 3 mm 3 mm 256 mm 75 mm 745 mm 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm 745 mm 256 mm 75 mm 75 mm 75 mm 75 mm Array Installation section Landscape...

Page 13: ...g cautions Be aware of the necessary grounding requirements prior to installation Your local authorities can help you further Install arrestors surge absorbers or any other appropriate lightning prote...

Page 14: ...r Cables drooping from the terminal box are hazardous and must be avoided Cables should be secured so they are not exposed to direct sunlight such as behind the module The sum of Voc of modules in ser...

Page 15: ...ny other hard materials use only soft cloths or sponges for removing dirt from the SF modules surface When replacement parts are required be sure the installer servicer uses parts specified by the man...

Page 16: ...iafilmplatz 8 82031 Gr nwald bei M nchen Germany Tel 49 89 92 86 142 0 Italy Solar Frontier Europe GmbH Sede Secondaria per l Italia Via Domenico Cotugno 49 A scala B 70124 Bari Italy Tel 39 080 90 21...

Reviews: